How To Change Sensitivity For A Detector; How To Select A Detector; How To Use The Detector Sensitivity Screen - Notifier NFS-640 Programming Manual

Fire alarm control panel
Hide thumbs Also See for NFS-640:
Table of Contents

Advertisement

3. Status Change

How to Change Sensitivity for a Detector

Status Change
Password

How to Select a Detector

Enter the SLC address (2D101) of an installed detector in the "LDAAA" field (shown above). The
control panel displays the following screen:

How to Use the Detector Sensitivity Screen

Use the instructions below to set/change detector sensitivity, display additional detectors, and set Pre-
alarm values.
Note: If not using Pre-Alarm, set PA=0. PA=1 is the self-optimizing mode. For details, refer to "How to Select a Pre-
Alarm Level" on page 89.
48
www.PDF-Zoo.com
The Detector Sensitivity option lets you change the Alarm and Pre-Alarm
(sensitivity) level for an installed detector. From the "Status Change Selection"
screen, press the 2 key to display the "Detector Selection" screen as shown below:
DET. SENS. & COMP.
PROGRM SMOKE(PHOTO) DETECTOR ADDR 2D101
To
Display detector information
on the screen.
Set alarm sensitivity level.
Set Pre-alarm level
Save the sensitivity values.
Display the next existing
detector address.
Display the previous existing
detector address.
How to Change Sensitivity for a Detector
ENTER POINTS:LDAAA,E
03 __ __ __ __A8P8AV 2D101
Alarm Level
Enter or Press
The detector address, then press
A value (1-9) or increase or decrease values by pressing
the
or
keys:
NEXT
PREVIOUS
A value (0-9) or increase or decrease values by pressing
the
or
keys:
NEXT
PREVIOUS
(Next Selection)
(Previous Selection)
NFS-640 Programming Manual P/N 51333:B 10/03/2003