How to Program a Releasing Zone
NFS-640 Programming Manual P/N 51333:B 10/03/2003
www.PDF-Zoo.com
Smoke
Detector
2D102
CBE list = Z01 ZR1
Figure 11 Illustrated Example of Cross Zone Programming
A listing of each Cross Zone option and the conditions required to activate the Releasing Zone,
according to the example shown above.
Cross Zone
Selection (Cross=)
Cross=N
Cross=Y
Cross=Z
Cross=H
Select a time for the Releasing Zone Delay Timer (refer to"How to Program a Delay Timer" on page 54.)
To Program
Cross Zones
Press
at this point to save the Cross Zone value if no other fields on the screen are changing. To
change another field on the screen, move the cursor into position by pressing the arrow keys on the
keypad.
Software
Zone Z01
CBE list = Z02 ZR1
Heat
Software
Detector
Zone Z02
2D104
Releasing
Zone ZR1
REL
B03
Condition(s) Required to Activate the Releasing zone
An alarm from any detector activates the releasing circuit.
An alarm from any two detectors activates the releasing circuit.
An alarm from two detectors mapped to different Software Zones,
but mapped to the same Releasing Zone.
• An alarm from 2D101 and 2D103
• An alarm from 2D102 and 2D104
• An alarm from 2D101 and 2D104
• An alarm from 2D102 and 2D103
The two detectors listed in each set above are each mapped to
different zones, but both list ZR1 in their CBE.
Activation of heat detector 2D104 and one smoke detector (2D101,
21D102, or 2D103).
Do this
Type N, Y, Z, or H in the
CROSS=
keys,
or
, until N, Y, Z or H appears in the that field.
Appendix A: Releasing Applications
Smoke
Smoke
Detector
Detector
2D103
2D101
CBE list = Z01 ZR1
CBE list = ZR1
field, or press the
or
NEXT
PREVIOUS
63