How To Modify An Addressable Monitor Module Point; Monitor Module Default Zone Assignments - Notifier NFS-640 Programming Manual

Fire alarm control panel
Hide thumbs Also See for NFS-640:
Table of Contents

Advertisement

How to Use the Basic Program
NFS-640 Programming Manual P/N 51333:B 10/03/2003
www.PDF-Zoo.com

How to Modify an Addressable Monitor Module Point

When you select a point address, the control panel returns a screen that displays information about the
point. Below is an example of information for a monitor module (2M101) in the LCD display:
PROGRAM MONITOR
HALLWAY
12 spaces for extended
custom label
Field
Description
Type Code
Monitor Module function specification
- MONITOR in example.
Custom Label
20 character custom label.
Extended Label 12 character custom label extension.
CBE List
Five zones can be listed - one zone,
Z09, is shown in the example. Up to 4
more could be added to this module.
Table 5 Modifying Monitor Module Programming Selections
Modifying Control Module Programming Selections
When finished modifying a point, press the
another point.

Monitor Module Default Zone Assignments

Listing of the monitor module address range and the default zone assignment for each range:
Blinking Type Code selection
WESTERN ENTRANCE AND
09 __ __ __ __
Default zone
CBE list
(five zones)
Set as Follows
Press the
valid monitor module Type Code selections. Lists and
descriptions are in See Table 33 on page 105.
Change by placing the cursor into the first space of the field
using the arrow keys, then typing the descriptor.
Note: Spaces must be input by the user, including any space
necessary between the custom and extended label fields. An 80-
column printout will run the two fields together.
See "Custom Label" above.
Zones can be changed or added to the CBE list by placing the
cursor in the zone field using arrow keys, then typing.
See Table 6 on page 23 for defaults.
key; then press the
ENTER
Monitor Module Address
01 through 19
20 through 39
40 through 59
60 through 79
80 through 99
100 through 119
120 through 139
140 through 159
Table 6 Monitor Module Default Zones
2. Program Change
20-character user-editable custom label.
2M101
SLC address (001-159)
M (module)
SLC number (1 or 2)
or
Selection keys to scroll through
NEXT
PREVIOUS
or
NEXT
PREVIOUS
Zone Default
Z04
Z05
Z06
Z07
Z08
Z09
Z10
Z11
key to select
23