Viewing Walk Test Results - Notifier NFS-640 Programming Manual

Fire alarm control panel
Hide thumbs Also See for NFS-640:
Table of Contents

Advertisement

3. Status Change
CLIP mode - Once the test is started:

Viewing Walk Test Results

When finished with a Walk Test, view the History buffer, installed printers and CRT-2s to check the
results of the Walk Test. View the History buffer by using the Read Status function. From the SYSTEM
NORMAL screen, press the
History buffer. For further instructions on using the Read Status function, refer to the NFS-640
Operations Manual.
52
www.PDF-Zoo.com
37
3 blinks, stop, 7 blinks, long stop, 3 blinks, stop, 7 blinks, long stop,....
70
7 blinks, stop, 10 blinks, long stop, 7 blinks, stop,.....
107
10 blinks, stop, 7 blinks, long stop, 10 blinks, stop,.....
152
15 blinks, stop, 2 blinks, long stop, 15 blinks, stop, 2 blinks, long stop....
• an input device activated in Basic Walk Test latches on steady green for the duration of the test.
• an output device activated in Basic Walk Test will remain active and the LED will glow steady
green for
- approximately 4 seconds for alarms
- approximately 8 seconds for troubles.
• an output device activated in Advanced Walk Test will remain active and the LED will glow
steady green until the reset key is pressed.
• intelligent addressable input and output devices continue to blink red as usual until activated.
• an input device activated in Basic Walk Test latches on steady red during activation. If the device
is put in trouble (for instance, the detector head is removed, then replaced), the LED will be
latched on for the duration of the test.
• an output device activated during Basic Walk Test will remain active and the LED will glow
steady green (if a FlashScan module) or steady red (if a CLIP module) for
- approximately 4 seconds for alarms
- approximately 8 seconds for troubles.
• an output device activated in Advanced Walk Test will remain active and the LED will glow
steady green (if a FlashScan module) or steady red (if a CLIP module) until the reset key is
pressed.
ENTER
key, press the 2 key two times, then press the
NFS-640 Programming Manual P/N 51333:B 10/03/2003
How to Do a Walk Test
key to view the
ENTER

Advertisement

Table of Contents
loading

Table of Contents