Battery Type And Capacities - Notifier INERTIA-2464/64 Technical/Programming Manual

Fire indicator panel
Table of Contents

Advertisement

INERTIA-2464 Technical & Programming Manual
PERFORMANCE DATA
27VDC Power Supply.
AC Input
Output Current
Output Voltage
Current Limit
Output Ripple
Internal 5VDC 2A Power Supply.
This supply's primary function is to power all internal operations of the FIP, ie: Microprocessor, liquid crystal
display, LED's keypad etc.
AC Input
Output Current
Output Voltage
Current Limit
Output Ripple

BATTERY TYPE AND CAPACITIES

ZONES FITTED
24 to 32
40 to 64
30 VAC +10% - 15%
3 AMPS (Incl 1A External)
27.6 VDC
3 AMPS
50 mV
30 VAC +15% or 27.6VDC+15%
2.0 AMPS
5.0 VDC
2.0 AMPS
150 mV
BATTERIES REQUIRED
2 X 12V 10 A/H
2 X 12V 17 A/H
Copyright (c) 1996, INERTIA FIRE SYSTEMS