How to Program a Releasing Zone
Description
How to program
How it works
Example 1 - Delay
Time Does Not Exceed
120 Seconds
NFS-640 Programming Manual P/N 51333:B 10/03/2003
www.PDF-Zoo.com

Programming an NYC Abort Switch

The following contains information needed to program an NYC Abort Switch:
A standard NYC delay timer that adds 90 seconds to the programmed Delay Timer.
Note: An NYC timer does not comply with UL Standard 864.
1.
Program the monitor module connected to the abort station with the Type Code
ABORT SWITCH
Point" on page 23.
2.
Select a time for the Releasing Zone Delay Timer (refer to"How to Program a
Delay Timer" on page 54).)
To Program
NYC Abort Switch
3.
Press
screen are changing. To change another field on the screen, move the cursor into
position by pressing the arrow keys on the keypad.
When an alarm initiates in the programmed Releasing Zone, pressing and holding the
Abort switch stops the Delay Timer countdown. The Delay Timer restarts at the
beginning of its countdown when the Abort switch is released. When the Delay Timer
expires, the 90-second NYC timer starts counting down. When both timers expire, the
control panel activates Releasing Zone outputs.
Note: 120 seconds is the maximum delay after the Abort switch is released. If the Delay Timer time
plus the NYC delay time of 90 seconds exceeds 120 seconds, Releasing Zone outputs will still be
activated at 120 seconds after the Abort switch is released.
Select a Delay Timer value for R05 of 15 seconds. The Releasing Zone activates and
the 15-second Delay Timer starts. Ten seconds into the Delay Timer countdown, press
and hold the Abort Switch for 30 seconds, then release the Abort Switch. The control
panel restarts the Delay Timer at 15 seconds and adds the NYC delay of 90 seconds.
The delay timers will both expire at 105 seconds, and Releasing Zone outputs will
begin releasing at that time. Following is an example of a NYC Abort Switch and a
Delay Timer programmed to Releasing Zone R05:
PRG RELEASE FUNCTION RELEASE CONTROL
DELAY=15 ABORT=NYC CROSS=N SOK=0000
Delay=15 sec.
0 sec.
10 sec.
Alarm
Press and hold
the Abort Switch
Release Abort Switch---
At this point, the delay time
becomes the programmed delay
(15 sec.) plus 90 seconds (105
sec.) OR 120 seconds,
whichever is smaller
as detailed in "How to Modify an Addressable Monitor Module
Do this
Type NYC in the ABORT= field, or press the
keys,
or
at this point to save the Abort Switch value if no other fields on the
Program selections for Releasing Zone R05
Total time from alarm initiation to release:
10 + 30 + 105 = 145 seconds
Delay=15 sec.
105 sec. (15 + 90). Does not exceed 120 seconds.
30 sec.
Figure 8 NYC Abort Switch Example 1
Appendix A: Releasing Applications
or
NEXT
PREVIOUS
, until NYC appears in the field.
R05
NYC Delay=90 sec.
When all timers are expired (in this example,
145 seconds after alarm initiation, 105
seconds after the Abort switch has been
released) the control panel activates
Releasing Zone outputs
59