How to Use the Utility Program

How to Use the Utility Program
NFS-640 Programming Manual P/N 51333:B 10/03/2003
www.PDF-Zoo.com

Utility Program Options

From the "Program Change Selection" screen, press the 3 key to display the "Utility
Program" screen as shown below:
Program Change
Password
Descriptions of the four (4) options on the Utility Program screen:
Utility Option
Description
DYN.POLL
This option determines the polling speed for the SLC, which you can select as
Dynamic Poll
follows:
• Select Y if you want to optimize the SLC for a harsh noise environment
• Select N to optimize the response speed of the SLC (default).
TBL.REMIND
This option provides trouble resound selections to meet the requirements of NFPA
TBL Reminder
72-1999, which you can select as follows:
• Select * if you don't want a trouble reminder
• Select 1 to sound a short trouble reminder tone every minute
• Select 2 to resound a trouble tone every 24 hours at 11:00 AM, and to send a
reminder every sixty seconds for acknowledged troubles
• Select 3 to display a detector while in the alarm verification mode and no trouble
reminder
• Select 4 for once a minute trouble reminder with alarm verification display
• Select 5 for trouble reminder resound every 24 hours at 11:00 AM with alarm
verification display, and to send a reminder every sixty seconds for acknowledged
troubles
ALA.SCROLL
This option allows you to select how alarms are displayed.
Alarm Scroll
• Select Y if you want each alarm displayed for approximately two seconds (default)
• Select N if you want only the first alarm and the alarm count displayed
LOCAL
This option allows you to disable local control of the
CONTROL
DISPLAY
control as follows:
• Select N to disable local control
• Select Y to enable local control (default)
Note: If the panel is to be controlled exclusively by a Display and Control Center
(DCC), Local Control should be disabled.

How to Select Utility Program Options

To select utility options, follow these steps:
1.
Using the arrow keys, move the blinking cursor to a selection.
2.
Press the
or
NEXT
PREVIOUS
or *, 1, 2, 3, 4, 5 (TBL Reminder).
3.
When finished making selections, press the
normal operation.
DYN.POLL=N
TBL.REMIND=2
LOCAL CONTROL=Y
key,
key and
SIGNAL SILENCE
SYSTEM RESET
Table 26 Utility Program Options
key to select Y or N (Dynamic Poll, Alarm Scroll, or Local Control);
key three times to return the control panel to
ESC
2. Program Change
ALA.SCROLL=Y
/
ACKNOWLEDGE
SCROLL
key. You can select local
43