If the control panel indicates a fire alarm, you can do the following:
1.
To silence the panel sounder, press the
and
LED light steady.
ALARM SILENCED
The control panel sends an Alarm Silenced message to the History buffer and
installed printers, terminal mode LCD-80s, and CRT-2s. Figure 8 shows a sample
Alarm Silenced message.
$ODUP 6LOHQFHG
)LJXUH 
2.
Check the Alarm message for the location and type of trouble.
3.
Correct the condition causing the alarm.
4.
When you finish correcting the alarm condition, press the
return the control panel to normal operation (indicated by the "All Systems
Normal" message). The control panel sends an "All Systems Normal" message to
the LCD display, History buffer, and installed printers, terminal mode LCD-80s,
and CRT-2s.
+RZWR,QWHUSUHW)LUH$ODUP7\SH&RGHV
The Type Code that displays in the Alarm message indicates the function of the point
that initiates the fire alarm. For example, a monitor module with a
Code means that the monitor module connects to a manual pull station. Table 6 contains
a list of the Type Codes that can appear in an alarm message.
7DEOH  )LUH $ODUP 7\SH &RGHV
Type Code
Purpose
Activate an alarm-monitoring device
MONITOR
(latching)
Indicates activation of a manual
PULL STATION
(latching)
fire-activating device, such as a pull
station.
Indicates activation of a two-wire or
SMOKE DETECT
(latching)
four-wire smoke detector
Indicates activation of a conventional
HEAT DETECT
(latching)
heat detector
blank
Indicates activation of a device with
(latching)
no description
Indicates activation a waterflow alarm
WATERFLOW
(latching)
switch
.
Indicates activation of a monitor
MAN
RELEASE
(latching)
module programmed to a Releasing
Zone to perform a releasing function
When an alarm exists, activates the
SILENCE
(non-latching)
Alarm Silence function and lights the
ALARM SILENCED
How to Operate a Control Panel with a Fire Alarm
ALARM SILENCE
6WDWXV EDQQHU
$/$50 6,/(1&('
$ 78( 
7LPH DQG GDWH RI WKH $ODUP 6LOHQFHG
6DPSOH $ODUP 6LOHQFHG 0HVVDJH
What if does
Lights
activates CBE
Lights
activates CBE
Lights
activates CBE
Lights
activates CBE
Lights
activates CBE
Lights
activates CBE
Lights
activates CBE
Lights
and activates CBE
LED
AFC-600 Operations PN 51033:A 3/8/99
key. The
LED
FIRE ALARM
key to
SYSTEM RESET
Type
PULL STATION
LED and
FIRE ALARM
LED and
FIRE ALARM
LED and
FIRE ALARM
LED and
FIRE ALARM
LED and
FIRE ALARM
LED and
FIRE ALARM
LED and
FIRE ALARM
LED
ALARM SILENCED