Appendix A: Releasing Applications

How to Program a Manual Release Delay Switch

The following contains information needed to program a Manual Release Delay switch for a monitor module
Description
How to program
Example:
Releasing Zone R5.
For Example, program Releasing Zone R5 with a Manual Release Delay switch for the following
releasing selections:
68
www.PDF-Zoo.com
A monitor module—connected to a UL-listed manual station (such as the Notifier
NBG-12LRA)—used to initiate a manual release with 30-second delay time.
A Manual Release Delay switch overrides the FACP programmed Delay Timer in
certain circumstances, but not the soak timer.
Multiple monitor modules can be programmed with a
They work like multiple conventional manual release switches on a conventional
zone.
1.Select a monitor module (refer to "How to Modify or Delete a Point (2=
page 20) that you want to use for the manual release function.
2.Select the
MANREL DELAY
PROGRM MANREL_DELAY MODULE ADDR 2M101
3.Select the Releasing Zone (R0-R9) for your releasing application.
4.Press the
ENTER
Change screen.
A programming example of a Monitor Module module programmed for
SYSTEM
NORMAL
NBG-12LRA
station with
Manual Release
Lever
Figure 14 Monitor Module Configured as a Manual Release Delay Switch
PRG RELEASE FUNCTION RELEASE CONTROL
DELAY=60 ABORT=ULI CROSS=N SOK=0030 R05
When the Manual Release Delay Switch activates, the control panel replaces the
Delay Time with 30 seconds if the Delay Timer has not counted down below 30
seconds. If the Delay Timer has counted down to 30 seconds or less, no change is
Type Code.
Type Code selection:
R5 __ __ __ __
Releasing Zone selection (R5 shown)
key to save, then press the
ESC
SYSTEM
ACTIVATED
Monitor
Module
Type Code
MANREL DELAY
B01
NFS-640 Programming Manual P/N 51333:B 10/03/2003
How to Program a Releasing Zone
Type Code.
MANREL DELAY
POINT
_
MANREL
DELAY
2M101
key until you return to the Program
switch for
MANREL DELAY
Detector
R05
Control
Module
)" on