Section 1 Operating Information
Normal Standby Operation.
1. Green P
indicator lit steadily.
OWER
2. Red F
A
indicator off.
IRE
LARM
3. Yellow T
indicators off.
ROUBLE
Alarm Condition.
1. Red F
A
indicator lit.
IRE
LARM
2. Alarm signaling devices activated.
3. Option module (remote station or supplementary alarm relay) activated.
4. Alarm information visible on LCD (liquid crystal display).
Alarm Reset.
After locating and correcting the alarm condition, reset
the control panel by pressing the S
Trouble Condition.
Activation of trouble signal under normal
operation indicates a condition that requires immediate attention. Contact
your local service representative. Silence the audible signal by pressing the
A
switch. The trouble indicator will remain illuminated.
CKNOWLEDGE
Section 2 NFS2-3030 Switch Functions
A
.
This silences the piezo sounder and changes all flashing
CKNOWLEDGE
conditions to steady. It sends an acknowledge message to the printer and
history file. A
also automatically sends a special command to
CKNOWLEDGE
silence piezo sounders on ACS Annunciators. If more than one event exists,
it advances the display to the next item and displays it until the
A
switch is pressed again. Only one press is necessary for
CKNOWLEDGE
non-fire, trouble, or supervisory signals.
S
S
.
S
S
IGNAL
ILENCE
IGNAL
illuminates the S
S
IGNALS
ILENCED
S
message to the LCD, printer, and history file. A subsequent alarm
ILENCED
will then resound the system.
Notes:
1. This system is programmed to inhibit signal silence for ____seconds.
2. This system is programmed to automatically silence alarm signal after
_____ minutes.
D
.
The NFS2-3030 waits for the D
RILL
then turns on all silenceable circuits (all control modules/panel circuits that are
programmed silenceable for fire alarms), and turns off the S
LED. This event shows on the LCD, printer, and History file.
Note: This switch is only available on NFS2-3030 with keypad/display.
S
R
.
Resets the control panel in standalone applications.
YSTEM
ESET
Resets panel when enabled in network applications.
L
T
.
Press and hold the switch to lamp-test the LEDs.
AMP
EST
Section 3 LED Indicators
Controls Active.
Green LED which illuminates when the NFS2-3030
assumes control of the network primary display.
Power .
Green LED which illuminates when primary power is applied to
the control panel.
Fire Alarm.
Red LED that flashes when one or more alarms occur.
Illuminates steadily after alarms are acknowledged, and turns off when
S
R
is pressed after alarm clears.
YSTEM
ESET
Pre-Alarm.
Red LED that flashes when a pre-alarm threshold is reached.
NFS2-3030 OPERATING INSTRUCTIONS
R
switch.
YSTEM
ESET
turns off all silenceable circuits and
ILENCE
indicator. It also sends a S
IGNALS
switch to be pressed for 2 seconds,
RILL
IGNALS
This sheet must be framed and mounted adjacent to the control panel.
Document 52547 Rev B ECN 08-364 8/18/2008
Security.
after the alarm clears and S
Supervisory.
condition occurs, such as a sprinkler valve tamper condition. The LED
illuminates steady after conditions are acknowledged, and turns off when the
conditions are cleared. The Tamper indication will latch until S
is pushed.
System Trouble.
occur. Goes on steadily when A
all trouble conditions are cleared.
Other Event.
or weather alert occurs. Goes on steadily when A
and turns off when the condition is cleared.
Signals Silenced.
S
has been pressed. Turns off when D
ILENCED
pressed.
Point Disabled.
are disabled. The LCD will indicate which points have been disabled. Turns
off when points are re-enabled.
CPU Failure.
Section 4 NFS2-3030 Audible Sounder
Alarm.
A continuous sounding tone.
Trouble, Disable, Prealarm.
Supervisory.
Security.
Section 5 Periodic Testing and Maintenance
To ensure proper and reliable operation, system inspection and testing should
be scheduled monthly, or as required by NFPA 72 or local fire codes. A
qualified Service Representative should perform testing.
Before Testing:
station if alarm condition is transmitted. Notify facility personnel of the test
so alarm sounding devices are ignored during the test period. Physically
disconnect releasing devices.
S
ILENCED
Remote Connection Feature:
UDACT and TM-4 be disconnected during annual testing to prevent
transmission of false alarms.
UDACT: Disable by turning the internal AKS-1 keyswitch.
TM-4: Slide SW4 Disable All Output switch from "Enable" to "Disable."
After Testing:
on. Notify all fire, central station, and/or building personnel when testing is
complete. Re-connect releasing devices.
Section 6 Local Service Representative:
NAME: ________________________________________________
ADDRESS: _____________________________________________
TELEPHONE NUMBER: ________________________________
Blue LED that illuminates for a security alarm. LED turns off
R
is pressed.
YSTEM
ESET
Yellow LED that flashes when a Supervisory or Tamper
Yellow LED that flashes when one or more troubles
CKNOWLEDGE
Yellow LED flashes when a process monitor, hazard alert
Yellow LED that illuminates after S
Yellow LED that illuminates when one or more points
Yellow LED that illuminates if the microprocessor fails.
Two beeps per second.
Four beeps per second.
Eight beeps per second.
Notify fire department and/or central alarm receiving
ULC requires that devices such as
Verify that remote-connection devices are turned back
R
YSTEM
ESET
is pressed, and turns off when
is pressed,
CKNOWLEDGE
IGNALS
or S
R
is
RILL
YSTEM
ESET