4.17 Communication operation and setting

Purpose
Communication operation from
PU connector
Restrictions on parameter write
through communication
Operation selection at a
communication error

4.17.1 Wiring and configuration of PU connector

Using the PU connector, you can perform communication operation from a personal computer, etc.
When the PU connector is connected with a personal, FA or other computer by a communication cable, a user program can
run and monitor the drive unit or read and write to parameters.
(1)
PU connector pin-outs
NOTE
 Pins No. 2 and 8 provide power to the parameter unit. Do not use these pins for RS-485 communication.
 When making RS-485 communication between the FR-D700-G series, FR-E500 series, FR-S500 series and FR-F500J
series, incorrect connection of pins No.2 and No.8 (parameter unit power supply) of the above PU connector may
result in the drive unit malfunction or failure.
 When multiple drive units are connected using pins No.2
and No.8, power is provided from the drive unit which is
powered ON to the drive units which are powered OFF in
case drive units which are powered ON and OFF are
mixed. In such case, a protective circuit of the drive unit,
which is ON, is activated to stop communication.
When connecting multiple drive units for RS-485
communication, make sure to disconnect cables from
No.2 and No.8 so that pins No.2 and No.8 are not
connected between drive units.
 When using the RS-485 converter which receives power
from the drive unit, make sure that power is provided from
one drive unit only. (Refer to the figure below.)
 Do not connect the PU connector to the computer's LAN board, FAX modem socket or telephone modular connector.
The product could be damaged due to differences in electrical specifications.
Initial setting of computer link
communication (PU connector)
MODBUS RTU communication
specifications
Communication EEPROM write
selection
Stop mode selection at
communication error
Drive unit
(receptacle side)
viewed from bottom
8)
to
1)
Computer
Station 1
RS-232C
Drive unit
connector
PU
connector
RS-232C
RS-485
converter
Distributor
Connect pins No.2 and No.8
of one drive unit and a converter only.
Power supply

Communication operation and setting

Parameter that should be Set
Pr. 117 to Pr. 124
Pr. 117, Pr. 118, Pr. 120,
Pr. 122, Pr. 343, Pr. 502,
Pr. 549, Pr. 779
Pr. 121, Pr. 122, Pr. 502, Pr. 779
Pin Number
Name
1)
SG
2)
3)
RDA
4)
SDB
5)
SDA
6)
RDB
7)
SG
8)
When pins No.2 and No.8 are connected
ON
Protective
Drive unit,
circuit
Inverter
operation
PU
(shut-off)
connector
Communication
stop
Station 2
Station n
Drive unit
Drive unit
PU
PU
connector
connector
Terminating resistor
Do not connect pins No.2 and No.8
of the other inverters.
Refer to Page
184
203
Pr. 342
190
185
Description
Earth (ground)
(connected to terminal 5)
Parameter unit power supply
Drive unit receive+
Drive unit send-
Drive unit send+
Drive unit receive-
Earth (ground)
(connected to terminal 5)
Parameter unit power supply
OFF
OFF
Drive unit,
Drive unit,
Inverter
Inverter
PU
PU
connector
connector
Power supply
4