Insulation Resistance Test Using Megger; Pressure Test - Mitsubishi Electric FR-D720-0.2K-G Instruction Manual

S-pm geared motor drive unit fr-d700-g series
Table of Contents

Advertisement

Measurement of main circuit voltages, currents and powers
6.2.8

Insulation resistance test using megger

 For the drive unit, conduct the insulation resistance test on the main circuit only as shown below and do not perform the test
on the control circuit. (Use a 500VDC megger.)
NOTE
 Before performing the insulation resistance test on the external circuit, disconnect the cables from all terminals of
the drive unit so that the test voltage is not applied to the drive unit.
 For the continuity test of the control circuit, use a tester (high resistance range) and do not use the megger or buzzer.
6.2.9

Pressure test

Do not conduct a pressure test. Deterioration may occur.
282
R/L1
Power
S/L2
supply
T/L3
500VDC
Drive unit
megger
Earth (Ground)
Motor
U
M
V
W