Drive Unit And Peripheral Devices; Drive Unit Placement - Mitsubishi Electric FR-D720-0.2K-G Instruction Manual

S-pm geared motor drive unit fr-d700-g series
Table of Contents

Advertisement

1.2

Drive unit and peripheral devices

AC power supply
Use within the permissible power supply
specifications of the drive unit. To ensure
safety, use a molded case circuit breaker,
earth leakage circuit breaker or magnetic
contactor to switch power ON/OFF.
(Refer to page 284.)
Molded case circuit breaker (MCCB)
or earth leakage circuit breaker
(ELB), fuse
The breaker must be selected carefully
since an in-rush current flows in the
drive unit at power on.
(Refer to page 4.)
Magnetic contactor (MC)
Install the magnetic contactor to ensure
safety. Do not use this magnetic contactor
to start and stop the drive unit. Doing so will
cause the drive unit life to be shorten.
(Refer to page 44.)
Reactor (FR-HAL, FR-HEL option)
Reactors (option) must be used when
power harmonics measures are taken,
the power factor is to be improved or the
drive unit is installed near a large power
supply system (500kVA or more). The
drive unit may be damaged if you do not
use reactors. Select the reactor according
to the model. Remove the jumpers across
terminals P/+ and P1 to connect the DC reactor.
AC reactor (FR-HAL)
Noise filter (ferrite core) ∗
(FR-BSF01, FR-BLF)
Install a noise filter (ferrite core)
to reduce the electromagnetic
noise generated from the drive
unit. Effective in the range from
about 1MHz to 10MHz. When
more wires are passed through,
a more effective result can be
obtained. A wire should be
wound four turns or more.
Filterpack (FR-BFP2), which contains DC reactor and noise filter in one package, is also available.
High power factor
converter (FR-HC2)
Power supply harmonics
can be greatly suppressed.
: Install this as required.
Parameter unit
(FR-PU07)
DC reactor (FR-HEL) ∗
Drive unit
(FR-D700-G)
P/+
P1
Noise filter
(capacitor) ∗
(FR-BIF)
Reduces the
radio noise.
Brake unit
(FR-BU2)
Power regeneration
Resistor unit (FR-BR)
common converter
Discharging resistor (GZG, GRZG)
(FR-CV)
Great braking capability
The regenerative braking capability
is obtained.
of the drive unit can be exhibited fully.

Drive unit and peripheral devices

Enclosure surface operation
panel (FR-PA07)
By connecting the connection
cable (FR-CB2) to the PU
connector, operation can be
performed from FR-PU07,
FR-PA07.
(Refer to page 25.)
RS-485
RS-232C
Converter
Earth
(Ground)
R/L1 S/L2 T/L3
P/+ N/-
Devices connected to the output
P/+
PR
Do not install a power factor correction capacitor, surge
suppressor or noise filter (capacitor) on the output side
P/+
of the drive unit. When installing a molded case circuit
PR
breaker on the output side of the drive unit, contact
each manufacturer for selection of the molded case
circuit breaker.
Earth (Ground)
To prevent an electric shock, always earth (ground) the
motor and drive unit. For reduction of induction noise
from the power line of the drive unit, it is recommended
to wire the earth (ground) cable by returning it to the
earth (ground) terminal of the drive unit.
RS-232C - RS-485 converter is
required when connecting to PC
with RS-232C interface.
(Refer to page 181.)
Brake resistor (FR-ABR,
MRS type, MYS type)
Braking capability can be improved.
(0.4K or higher)
(Refer to page 27.)
P/+
PR
Noise filter (ferrite core)
(FR-BSF01, FR-BLF)
U
V
W
Install a noise filter (ferrite
core) to reduce the
electromagnetic
noise generated from the
drive unit. Effective in the
range from about 1MHz to
10MHz. A wire should be
wound four turns at a
maximum.
Contactor
Example: No-fuse switch
(DSN type)
Install a contactor in an
application where the PM
motor is driven by the load
even at power-OFF of the
drive unit. Do not open or
close the contactor while
the drive unit is running
(outputting).
Motor
Earth
(Ground)
1