Check first when you have a trouble

POINT
 If the cause is still unknown after every check, it is recommended to initialize the parameters (initial value) then
set the required parameter values and check again.
5.5.1

Motor does not start

Check
Points
Appropriate power supply voltage is not applied.
(Operation panel display is not provided.)
Main
Circuit
Motor is not connected properly.
The jumper across P/+ to P1 is disconnected.
Start signal is not input.
Both the forward and reverse rotation start signals (STF,
STR) are input simultaneously.
Speed command is zero.
(RUN LED on the operation panel is blinking.)
AU signal is not ON when terminal 4 is used for speed
setting.
(RUN LED on the operation panel is blinking.)
Output stop (MRS) signal or reset (RES) signal is ON.
Input
(RUN LED on the operation panel blinks while MRS
Signal
signal is ON.)
Jumper connector of sink - source is wrongly selected.
(RUN LED on the operation panel is blinking.)
Shorting wires between S1 and SC, S2 and SC are
disconnected.
Voltage/current input switch is not correctly set for analog
input signal (0 to 5V/0 to 10V, 4 to 20mA).
(RUN LED on the operation panel is blinking.)
was pressed.
(Operation panel indication is
Two-wire or three-wire type connection is wrong.
Possible Cause
(PS).)

Check first when you have a trouble

Countermeasures
Power ON moulded case circuit breaker (MCCB), an
earth leakage circuit breaker (ELB), or a magnetic
contactor (MC).
Check for the decreased input voltage, input phase loss,
and wiring.
Check the wiring between the drive unit and the motor.
Securely fit a jumper across P/+ to P1.
To use a DC reactor (FR-HEL) or Filterpack, remove the
jumper across the terminals P/+ and P1, then connect
the DC reactor or Filterpack.
Check the start command source, and input a start
signal.
PU operation mode:
External operation mode : STF/STR signal
Turn ON only one of the forward and reverse rotation
start signals (STF or STR).
If the STF and STR signals are turned ON
simultaneously in the initial setting, a stop command is
given.
Check the speed command source and enter a speed
command.
Turn ON the AU signal.
Turning ON the AU signal activates terminal 4 input.
Turn MRS or RES signal OFF.
Drive unit starts the operation with a given start
command and a speed command after turning OFF
MRS or RES signal.
Before turning OFF, ensure the safety.
Check that the control logic switchover jumper connector
is correctly installed.
If it is not installed correctly, input signal is not
recognized.
Short between S1 and SC, S2 and SC with shorting
wires.
Set Pr. 73, Pr. 267, and a voltage/current input switch
correctly, then input an analog signal in accordance with
the setting.
During the External operation mode, check the method
of restarting from a
input stop from PU.
Check the connection.
Connect STOP signal when three-wire type is used.
Refer
to
Page
15
33
166
18
166
147
119,
252
20
19
5
18
256
121
265