(b) Method to adjust any point without application of a voltage (current) across terminals 2 and 5 (4 and 5)
(To change from 4V (80%) to 5V (100%))
Operation
1.
Confirm the operation status indicator and
operation mode indicator
 The drive unit should be at a stop.
 The drive unit should be in the PU operation
mode. (Use
)
2.
Press
to choose the parameter setting
mode.
3.
Turn
until "
" appears.
4.
Press
to display "
5.
Turn
until "
" ("
Set to C4 Terminal 2 speed setting gain.
6.
Press
to display the analog voltage
(current) value (%).
7.
Turn
to set gain voltage (%).
"0V(0mA) is 0%, 10V(5V, 20mA) is 100%"
REMARKS
The current setting at the instant of turning
displayed.
You cannot check after performing operation in step 7.
8.
Press
to set.
to read another parameter.
Turn
Press
to return to the "
Press
twice to show the next parameter ("
REMARKS
By pressing
You cannot check after performing operation in step 7.
Speed setting by analog input (terminal 2, 4)
".
") appears.
Blink...Parameter setting complete!!
" indication (step 4).
after step 6, you can confirm the current speed setting bias/gain setting.
Display
PRM indicator is lit.
(The parameter number read previously appears.)
C0 to C7 settings
are enabled.
Terminal 2 input is
Terminal 4 input
selected
is selected
Analog voltage (current) value (%)
across terminals 2 and 5 (across
terminals 4 and 5)
The gain speed is reached when
the analog voltage (current) value
across terminals 2 and 5 (across
terminals 4 and 5) is 100%.
is
A
Terminal 2 input
is selected
(Adjustment completed)
").
Terminal 4 input
is selected
4
155