Types of Monitor
Unit
Electronic thermal
relay function load
0.1%
factor
Output current peak
0.01A
value
Converter output
0.1V
voltage peak value
Output power
0.01kW
Input terminal status
—
Output terminal
—
status
Cumulative
1h
energization time
Reference voltage
—
output
Actual operation time
1h
,
Motor load factor
0.1%
Cumulative power 0.01kWh
PID set point
0.1%
PID measured value
0.1%
PID deviation
0.1%
Drive unit I/O terminal
—
monitor
Motor thermal load
0.1%
factor
Drive unit thermal
0.1%
load factor
PTC thermistor
0.01k
resistance
Monitor display and monitor output signal
Pr. 52 Setting
Operation
PU
Pr. 54 (FM)
panel
main
Setting
LED
monitor
10
10
11
11
12
12
14
14
—
20
—
21
23
24
24
25
52
52
53
53
54
55
61
61
62
62
64
Terminal FM
Full Scale Value
Displays the thermal cumulative value on
the assumption that the thermal operation
100%
level is 100% (Larger thermal between the
motor thermal and transistor thermal).
Holds and displays the peak value of the
Pr. 56
output power monitor.
(Cleared at every start)
Holds and displays the peak value of the
200V class: 400V
DC bus voltage value.
400V class: 800V
(Cleared at every start)
Displays the power on the drive unit output
Rated drive unit
power 2
side
Displays the input terminal ON/OFF status
—
on the operation panel.
(Refer to page 137.)
Displays the output terminal ON/OFF
—
status on the operation panel.
(Refer to page 137.)
Adds up and displays the energization time
after drive unit shipment.
—
You can check the numbers of the monitor
value exceeded 65535h with Pr. 563.
Terminal FM:
—
Output 1440 pulse/s
Adds up and displays the drive unit
operation time.
You can check the numbers of the monitor
—
value exceeded 65535h with Pr. 564.
Can be cleared by Pr. 171. (Refer to page
138.)
Displays the torque in percentage on the
200%
assumption that the rated motor torque is
100%.
Adds up and displays the power amount
based on the output power monitor.
—
Can be cleared by Pr. 170. (Refer to page
137.)
100%
Displays the set point, measured value and
100%
deviation during PID control (Refer to page
—
221 for details.)
Displays the ON/OFF status of the drive
unit input terminal and output terminal on
—
the operation panel (Refer to page 137 for
details.)
Motor thermal heat cumulative value is
Thermal relay
operation level
displayed.
(100%)
(Motor overload trip (E.THM) at 100%)
Transistor thermal heat cumulative value is
Thermal relay
operation level
displayed.
(100%)
(drive unit overload trip (E.THT) at 100%)
Displays the PTC thermistor resistance at
terminal 2 when PTC thermistor protection
—
is active.
(0.10k to 31.5k(Refer to page 101.)
Description
135
4