<Set point input calibration>
1) Setting with terminal 2 input
1.Apply the input voltage of 0% set point setting (e.g. 0V) across terminals 2 and 5.
2.Enter in C2 (Pr. 902) the speed which should be output by the drive unit at the deviation of 0% (e.g. 0r/min).
3.In C3 (Pr. 902), set the voltage value at 0%.
4.Apply the voltage of 100% set point (e.g. 5V) across terminals 2 and 5.
5.Enter in Pr. 125 the speed which should be output by the drive unit at the deviation of 100% (e.g. 3000r/min).
6.In C4 (Pr. 903), set the voltage value at 100%.
2) Setting with Pr. 133
(When both or one of C42 (Pr. 934) and C44 (Pr. 935) is "9999".)
For the set point, set a % converted value in the range of 0 to 100%.
(When both of C42 (Pr. 934) and C44 (Pr. 935) "9999".)
For the set point, set PID coefficient, which corresponds with 0 to 100%.
<Measured value calibration>
1) When both or one of C42 (Pr. 934) and C44 (Pr. 935) is "9999"
1.Apply the input current of 0% measured value (e.g. 4mA) across terminals 4 and 5.
2.Make calibration using C6 (Pr. 904).
3.Apply the input current of 100% measured value (e.g. 20mA) across terminals 4 and 5.
4.Make calibration using C7 (Pr. 905).
2) When both of C42 (Pr. 934) and C44 (Pr. 935) "9999"
1. Apply the input current of 0% measured value (e.g. 4mA) across terminals 4 and 5.
2. Set PID display value at 0% measured value (example: 15(C)) to C42 (Pr. 934) , and calibrate C43 (Pr. 934).
3. Apply the input current of 100% measured value (e.g. 20mA) across terminals 4 and 5.
4. Set PID display value at 100% measured value (example: 35(C)) to C44 (Pr. 935), and calibrate C45 (Pr. 935).
REMARKS
The speed set in C5 (Pr. 904) and Pr. 126 should be the same as set in C2 (Pr. 902) and Pr. 125 .
The results of the above calibration are as shown below:
Pr. 934,
Pr. 133
Pr. 935
Setting
Setting
Set point
9999
—
Set point
Both or one
is 9999
Set a % converted value in the
Other than
9999
Set point
Other than
9999
corresponding with 0 to 100%.
Set Point Setting
(Terminal 2)
(%)
100
Measured
Value
0
0
5 (V)
Set point signal input
(Pr. 133)
(%)
100
0
C5(Pr. 904)
Pr. 126
Set point setting
range of 0 to 100%.
(Pr. 133)
Measured
value
(%)
100
0
C42(Pr. 934)
C44(Pr. 935)
Set PID coefficient
Special operation and speed control
Measured Value
Manipulated Variable
(Terminal 4)
(%)
100
0
0
4
Manipulated
20
(mA)
Variable(r/min)
C6(Pr. 904)
C7(Pr. 905)
Measured value
input signal
C2(Pr. 902)
(%)
100
0
0
4
20
(mA)
C43(Pr. 934)
C45(Pr. 935)
Measured value
input signal
3000
(Pr. 125)
0
0
100
Deviation(%)
4
225