GSMX4G / GSMXCN4G Installation and Setup Guide
4204 Relay Outputs map to zones
First 4204 Zones (device
address entered in Prompt 16):
Relay 1 = Zone 1
Relay 2 = Zone 2
Relay 3 = Zone 3
Relay 4 = Zone 4
NOTE: Zone 4 status is not
reported when being used as the
conditional (armed) trigger zone.
When using the communicator in 4204 Emulation Mode, DO NOT enable the
communicator (or LRR) in control panel programming. Instead, enable 4204
relay module address(es) and program the appropriate relay activation
functions for the relay-zones being used. In some control panels, it is called
"relay programming" and in others it is called "output device programming."
It is recommended that "close and stay closed" (usually choice 2) action is
selected. Selection of momentary activation will cause the communicator to
generate an alarm and NOT a restore, even if the communicator is pro-
grammed to send a restore for the given zone.
In 4204 mode, messages are reported in ADEMCO High-Speed format. Zone
alarms (status 7) are reported with "1" (alarm) or "3" (restore) displayed in
the zone position for the respective zone (e.g. alarm on zone 2: 5155 5555 7;
restore 5355 5555 7). A supervision fault trouble message is automatically
sent if the communicator detects no activity on its connection to the control
panel. The message is: 5555 5515 5; restore message is: 5555 5535 5.

Programming Options

PROMPTS
ENTRY
1
Strt Prog
Mode?
(Y/N)_
2
Enter
Password
Second 4204 Zones (device address
entered in Prompt 16, plus 1):
Relay 1 = Zone 5
Relay 2 = Zone 6
Relay 3 = Zone 7
Relay 4 = Zone 8
NOTE: Zone 8 status is not reported
when being used as the conditional
(armed) trigger zone.
OPTIONS
[Y], [N]
Enters programming mode.
[0-9, A-F,
If a password has been previously
N, S, T, X,
assigned, this prompt appears.
Y]
Enter a 4-digit password
(0-9, A-F, N, S, T, X, Y).
The next prompt appears.
– 14 –