Honeywell GSMX4G Installation And Setup Manual page 22

Intellipath series 4g gsm communicator auto-selects optimum gsm path - 2g, 3g, or 4g
Hide thumbs Also See for GSMX4G:
Table of Contents

Advertisement

GSMX4G / GSMXCN4G Installation and Setup Guide
PROMPTS
ENTRY
21
GSM Flt
Time
(00 mins)_
22
only
Telco Zone
4204
(0)_
2-4204
OPTIONS
[01-99]
In the event the communicator
detects a communication path
[00] = not
failure, enter the time delay (in
used
minutes) before the communica-
tor notifies the control panel with
a trouble message. The control
panel can then notify the central
station.
UL/ULC NOTE: Must be one
(01) minute.
See "Important Information
4204: [1-4]
Regarding Zone Input Options"
2-4204:
on previous page.
[1-8]
Enter the zone number to be used
[0] = not
for Telco line fault reports. This
used
zone assignment must be unique
from the open/close zone selected
in Prompt 23.
4204 Mode: If any zone is
programmed for "report only if
armed," zone 4 cannot be used
as a Telco zone.
2-4204 Mode: If any zone is
programmed for "report only if
armed," zone 8 cannot be used.
NOTE: Connect the Telco line fault
output (or relay output programmed
for "Telco line fault") to the Telco
zone.
– 20 –