4.2 Configuration Settings
4.2 Configuration Settings
4.2.1 Unit Configuration
The settings for the unit such as input range, channels to be converted and optional functions
are specified in the configuration menu of tool software.
■
Setting method
The following procedure describes the process when the thermocouple multi-analog input unit
or RTD input unit has been already allocated in the I/O map.
1.
Select Options>FP7 Configuration in the menu bar.
2.
Select "I/O Map" in the field.
3.
Select the slot where the unit has been registered, and press the [Advanced] button.
" Thermocouple multi-analog input unit or RTD input unit setting" dialog box is displayed.
4.
Select items according to the conditions used.
Select optional settings as necessary.
5.
Click the [OK] button.
The set values will be effective when they are downloaded with programs as a project.
Settings
Group
Setting item
Basic
Power frequency
setting item
Conversion time
(Common)
Conversion processing
Basic
setting item
Range setting
(for each
(TC unit)
channel)
4-6
Settings
60Hz/50Hz
(Note 1)
25ms/5ms
Execute/Not execute
K1 (-100.0 to 600.0°C)
K2 (-200.0 to 1370.0°C)
J1 (-100.0 to 400.0°C)
J2 (-200.0 to 1200.0°C)
T (-270.0 to 400.0°C)
Thermoc
N (-270.0 to 1300.0°C)
ouple
R (0.0 to 1760.0°C)
S (0.0 to 1760.0°C)
B (0.0 to 1820.0°C)
E (-270.0 to 1000.0°C)
PLII (0.0 to 1390.0°C)
WRe5-26 (0.0 to 2315.0°C)
-10 to +10 V
Voltage
0 to +5 V
+1 to +5 V
Default
60 Hz
25 ms
Execute
(Note 2)
(Note 2)
-10 to +10 V
WUME-FP7TCRTD-04