Profibus Pa Pressure Transmitter - ABB 265GS Operating Instruction

Pressure transmitter
Table of Contents

Advertisement

5.9

PROFIBUS PA pressure transmitter

PROFIBUS PA transmitters are designed to be connected to the DP / PA segment coupler /
linking device. The permissible terminal voltage is within the range of 10.2 ... 32 VDC.
Use of a shielded cable is recommended. The shielding is bonded by means of the metal cable
gland.
IMPORTANT (NOTE)
The transmitter must be grounded.
The switch-on behavior corresponds to Draft DIN IEC 65C/155/CDV of June 1996. If the
transmitter is operated on an Ex segment coupler / linking device in accordance with
DIN EN 61 158-2 of October 1994, time-dependent current limiting may cause the maximum
number of devices to be reduced.
The "OUT" variable is transmitted cyclically. This consists of the output value and 1 byte of
status information. The output value is transmitted with 4 bytes as an IEEE 754 floating-point
type.
For additional information on PROFIBUS PA - including the subject "Identification numbers" -
please
suggestions 10/63-0.40". These can be obtained from the Internet site www.abb.com; additional
information is also available at www.profibus.com.
IM/265Gx/Ax-EN-07
refer
to
"Additional
265Gx, 265Ax
notes 41/15-110"
and
Electrical connections
the
data
sheet
"Installation
37

Advertisement