Digital Input - JUMO mTRON T Operating Manual

Measuring, control, and automation system analog input module 4-channel
Hide thumbs Also See for mTRON T:
Table of Contents

Advertisement

6.3

Digital input

In addition to the analog inputs the module provides a digital input.
The status of the digital input is indicated by a LED. The display corresponds to the output sig-
nal to the system bus.
Setup dialog
Parameter
Parameter
Mode: Delay
Inverting
TAG number
Signal suppres-
sion
?
Level at suppres-
sion
Alarm type
Alarm active at
Selection/settings
0 s to 65535 s
Inversion of the input signal
Normal
Inverse
7 characters
Digital selector (Inactive)
Chapter 6.1 "Digital selector", page
35
Output level during active signal suppression
No choice
Active
The alarm type is not set by default.
CollectiveAlarm
Event
High (1)
Low (0)
6 Configuration
Description
Delay time during change of input signal
from Low to High (or from High to Low in
the case of active inverting)
Not inverted
Inverted
Identification marking (documentation in
PLC)
Signal (high-active) for suppression of
the input signal
Low level (0)
High level (1)
Alarm results in collective alarm of the
module.
Alarm results in an entry (event text) in
the event list.
Alarm at high level (1)
Alarm at low level (0)
45