JUMO mTRON T Operating Manual page 58

Measuring, control, and automation system analog input module 4-channel
Hide thumbs Also See for mTRON T:
Table of Contents

Advertisement

7 Configuration – in setup program only
Measured value
The table below shows the admissable measured value range of the analog inputs, depending
on the chosen sensor (incl. physical offset, if applicable). These values are the minimum and
the maximum input values for the customer-specific linearization.
Sensor
RTD temperature probe
Thermocouple
Resistance transmitter
Resistance/potentiometer
Current 0 to 20 mA
Current 4 to 20 mA
Voltage 0 to 1 V
Voltage 0 to 10 V
Voltage 2 to 10 V
NOTE!
In the case of standard signals (current, voltage), the measured value is monitored (incl. phy-
sical offset, if applicable). The current and voltage values that are specified in the table repre-
sent the limits acc. to NAMUR recommendation NE 43. A measured value beyond these limits
causes an overange or an underrange (out-of-range).
Linearization
Depending on the type of linearization, either the domain or the co-domain of the linearization
is monitored.
 Chapter 7.1.1 "Grid points", page 59
 Chapter 7.1.2 "Formula", page 61
Linearized value
The linearized value is monitored with respect to the scale range (start, end). As a result, the
range of linearized values (incl. standardized offset, if applicable) is limited as follows:
Lower limit = minimum(start, end) - |end - start| × 0.0125
Upper limit = maximum(start, end) + |end - start| × 0.03125
NOTE!
A linearized value beyond these limits causes an overange or an underrange (out-of-range).
58
Lower limit
Upper limit
0 Ω
4000 Ω
0 mV
100 mV
0 %
100 %
0 %
100 %
-0.25 mA
20.625 mA
3.8 mA
20.5 mA
-0.0125 V
1.03125 V
-0.125 V
10.3125 V
1.9 V
10.25 V
Comment
Sliding contact position, as a per-
centage of the overall resistance
(max. 4000 Ω)
Sliding contact position, as a per-
centage of the overall resistance
(max. 4000 Ω)

Advertisement

Table of Contents
loading

Table of Contents