Appendix; Technical Data; Analog Inputs - JUMO mTRON T Operating Manual

Measuring, control, and automation system analog input module 4-channel
Hide thumbs Also See for mTRON T:
Table of Contents

Advertisement

9.1

Technical data

9.1.1

Analog inputs

General information
Number
A/D converter
Thermocouples
Designation
Fe-CuNi "L"
Fe-CuNi "J"
Cu-CuNi "U"
Cu-CuNi "T"
NiCr-Ni "K"
NiCr-CuNi „E"
NiCrSi-NiSi "N"
Pt10Rh-Pt "S"
Pt13Rh-Pt "R"
Pt30Rh-Pt6Rh "B"
W5Re-W26Re „C"
W3Re-W25Re "D"
W3Re-W26Re
Chromel-Copel
Chromel-Alumel
PLII (Platinel II)
Linear
Cold junction
Cold junction accuracy
1
The accuracy values refer to the maximum measuring range. Smaller measuring ranges lead to reduced lineariza-
tion accuracy.
4
Dynamic resolution up to 16 bit
Standard
Measuring range
-200 to +900 °C
DIN EN 60584
-200 to +1200°C
-200 to +600 °C
DIN EN 60584
-200 to +400 °C
DIN EN 60584
-200 to +1372 °C
DIN EN 60584
-200 to +1000 °C
DIN EN 60584
-100 to +1300 °C
DIN EN 60584
-50 to 1768 °C
DIN EN 60584
-50 to 1768 °C
DIN EN 60584
0 to 1820 °C
0 to 2320 °C
0 to 2495 °C
0 to 2400 °C
GOST 8.585-
-200 to +800 °C
2001
GOST 8.585-
-200 to +1372 °C
2001
0 to 1395 °C
0 to 75 mV
Pt100 internal
± 1 K
Measuring accu-
1
racy
≤ 0.1 % from -100 °C 300 ppm/K
≤ 0.1 % from -100 °C 300 ppm/K
≤ 0.1 % from -130 °C 300 ppm/K
≤ 0.1 % from -150 °C 300 ppm/K
≤ 0.1 % from -80 °C
≤ 0.1 % from -80 °C
≤ 0.1 % from -80 °C
≤ 0.15 % from 20 °C
≤ 0.15 % from 20 °C
≤ 0.15 % from 400 °C 300 ppm/K
≤ 0.15 % from 500 °C 300 ppm/K
≤ 0.15 % from 500 °C 300 ppm/K
≤ 0.15 % from 500 °C 300 ppm/K
≤ 0.15 % from -80 °C 300 ppm/K
≤ 0.10 % from -80 °C 300 ppm/K
≤ 0.10 % from -80 °C 300 ppm/K
≤ 0.1 %

9 Appendix

Ambient
temperature influ-
ence
300 ppm/K
300 ppm/K
300 ppm/K
300 ppm/K
300 ppm/K
300 ppm/K
69