Alarms - JUMO mTRON T Operating Manual

Measuring, control, and automation system analog input module 4-channel
Hide thumbs Also See for mTRON T:
Table of Contents

Advertisement

6.2.1

Alarms

Limit value monitoring with one or two alarms and various alarm types can be activated for each
analog input. In addition, this function is required in order to trigger the collective alarm of the
module if the event of deviation above or below the measuring range (out of range).
Setup dialog
Parameter
Parameter
Alarm type 1, 2
?
Limit value 1, 2
Kind of alarm 1, 2 The alarm type is not set by default.
Event text 1, 2
?
Switching differ-
ential
?
Alarm suppres-
sion
Alarm delay
Selection/settings
Off
Min. alarm
Max. alarm
-99999 to 0 to +99999
CollectiveAlarm
Event
Use default text or select other text from
the list.
0 to 99999
Digital selector (Inactive)
Chapter 6.1 "Digital selector", page
35
0 s to 65535 s
6 Configuration
Description
Monitoring is not active.
Alarm is issued if the limit value is not
met.
Alarm is issued if the limit value is
exceeded.
Limit value at which an alarm is issued.
Alarm results in collective alarm of the
module.
Alarm results in an entry (event text) in
the event list.
Text that is entered in the event list for
an alarm (if Alarm type = "Event").
Used to suppress constant switching
operations in the event of minor fluctua-
tions of the input signal around the limit
value.
Signal to activate the alarm suppression
Delay time for alarm activation
41