Formula - JUMO mTRON T Operating Manual

Measuring, control, and automation system analog input module 4-channel
Hide thumbs Also See for mTRON T:
Table of Contents

Advertisement

7.1.2

Formula

Customer-specific linearization is specified using a 4th order polynomial. The polynomial is cal-
culated for the entire linearization range.
Polynomial formula: y = X4*x
Setup dialog
Parameter
Parameter
Measuring range
start (Ymin)
Measuring range
end (Ymax)
X0
X1
X2
X3
X4
The co-domain of the linearization (linearized values, y-axis) is checked in the module and
limited as follows:
Co-domain lower limit = Ymin - 0.0125 × (Ymax - Ymin)
Co-domain upper limit = Ymax + 0.03125 × (Ymax - Ymin)
7 Configuration – in setup program only
4
3
+ X3*x
Selection/settings
-99999 to 0 to +99999
-99999 to 100 to +99999
-99999 to 0 to +99999
-99999 to 1 to +99999
-99999 to 0 to +99999
-99999 to 0 to +99999
-99999 to 0 to +99999
2
+ X2*x
+ X1*x + X0
Description
Start value of the y-axis
End value of the y-axis
Absolute component of the polynomial
(point of intersection with the y-axis)
Coefficient of the linear component (x)
Coefficient of the quadratic
component (x
Coefficient of the cubic component (x
Coefficient of the quartic component (x
2
)
3
)
4
)