4
Technical data

HighLine C control terminals

External supply voltage 24 V

4.7
HighLine C control terminals
4.7.1
External supply voltage 24 V
Labelling
X5/24E
X5/GI
Labelling
X4/24O
X4/GO
Labelling
X5/24I
X5/GI
80
Feature
Connection for external 24 V supply
voltage by a safely separated
power supply unit (required for
mains-independent supply of the
control electronics and the
communication module)
Suppression of voltage pulses
Polarity reversal protection
Current consumption
Capacity to be charged
GND, reference potential for digital signals
Feature
Connection for external 24 V supply
voltage by a safely separated
Power supply unit (required for the
supply of the digital outputs)
Suppression of voltage pulses
Polarity reversal protection
Current consumption
GND, reference potential for digital signals
Feature
24 V voltage output
for connection of the digital inputs via
potential-free contacts
Max. output current
Electric strength of external voltage
Excess current release
GND, reference potential for digital signals
Rated value
24 V in accordance with IEC 61131-2
19.2 ... 28.8 V
Residual ripple max.  5 %
SELV/PELV
Suppressor diode 36 V, bidirectional
When polarity is reversed: no function and no
destruction
Approx. 0.6 A during operation
Max. 1.5 A starting current for 100 ms
1000 F
Rated value
24 V in accordance with IEC 61131-2
19.2 ... 28.8 V
Residual ripple max.  5 %
SELV/PELV
Suppressor diode 36 V, bidirectional
When polarity is reversed: no function and no
destruction
Approx. 0.15 A if all digital outputsare loaded with rated
current
Rated value
External supply at 24E: voltage drop < 2.5 V
Internal supply: DC 18 ... 28 V
50 mA
+30 V
Automatically resettable
EDS84ASC552 EN 10.0