4.8.3

Resolver connection

Resolvers are connected to X7 (9-pole Sub-D socket).
To avoid interference injection, only use shielded motor and encoder cables if an encoder
is used.
You can connect and operate:
Resolvers
ƒ
– Parameterisation of the number of pole pairs in C00925
– Lenze setting: Number of pole pairs = 1.
Multipole resolvers with a number of resolver pole pairs  2
ƒ
Resolvers of other manufacturers
ƒ
Please ensure compliance with the technical limiting values of the resolver:
Description
Cable length (system cable is recommended)
Number of resolver pole pairs
Carrier frequency of the excitation voltage
Impedance
X7 /
Pin 1, 2
Pin 4, 5
Pin 6, 7
Pin 8, 9
EDS84ASC552 EN 10.0
+REF, -REF
Excitation voltage
Maximum excitation current
+COS, -COS
+SIN, -SIN
+KTY, -KTY
Technical data
TopLine C control terminals
Resolver connection
Rated value
Max. 150 m
1 ... n
4 kHz
Z
= (R
+ j X
) = 90.9 Ohms (max.)
RO
RO
RO
When a resolver with a lower rotor impedance (Z
connected, the integrated overload protection limits the
excitation current which impairs the signal quality and
may distort the determined actual values.
R.m.s. value: V = 7.07 V
Peak value: û = 10 V
R.m.s. value: I = 77.78 mA
Peak value: Î = 110 mA
Type: KTY 83-110, KTY 84, adjustable
4
) is
RO
87