Terminal Assignment Of The Power Connections - Lenze 8400 Hardware Manual

E84a series
Hide thumbs Also See for 8400:
Table of Contents

Advertisement

Strip cables
X105
E84AVxxx3034
E84AVxxx3734
E84AVxxx4534
How to proceed:
1. Strip motor cable and cable for motor temperature monitoring according to
specified dimensions.
2. Fold back the shield of the motor cable and motor temperature cable over the cable
sheath. Keep unshielded ends short.
3. Fix shield on the cable sheath (e.g. using a heat-shrinkable tube).
4. Fasten wire end ferrule to PE cable.
– The other cables may be wired without using wire end ferrules.
5. Connect the shields separately to the shield sheet using (metal) cable ties or shield
clamps.
– left: motor cable
– right: cable of motor temperature monitoring
– For strain relief of the cables, measures are required.
EDS84ASC552 EN 10.0
Devices in a power range of 30 ... 45 kW (3/PE AC 400 V)

Terminal assignment of the power connections

84MOTL001_a
U, V, W
b
c
e
2
[mm]
[mm
]
[Nm]
[AWG]
[lb-in]
16 ... 50
4.0
40 190 24
6 ... 0
35
Electrical installation
X106
PE
a
d
2
[mm]
[mm
]
[Nm]
[AWG]
[lb-in]
2.5 ... 25
4.0
250 16
240 40
12 ... 2
35
6
84MOTL001_b
T1, T2
f
g
h
2
[mm]
[mm
]
[AWG]
0.2 ... 1.5
10
24 ... 16
203