6
Electrical installation
6.1
Important notes
Danger!
Hazardous electrical voltage
Depending on the device, all power connections remain live up to 3 minutes
after the mains has been switched off.
Possible consequences:
ƒ
Protective measures:
ƒ
ƒ
Danger!
Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ
Protective measures:
ƒ
EDS84ASC552 EN 10.0
Death or severe injuries when touching the power terminals.
Wait for at least 3 minutes before working on the power terminals.
Make sure that all power terminals are deenergised.
Death or severe injuries when the device is touched in the event of a fault.
Implement the actions required in the EN 61800-5-1. Especially:
– Fixed installation
– PE connection must conform to standards (PE conductor diameter
2
10 mm
or PE conductor must be connected twice)