4.4
Overcurrent operation
The controllers can be driven at higher amperages beyond the rated current if the duration
of this overcurrent operation is time limited. Two utilisation cycles with a duration of 15
s and 180 s are defined. Within these utilisation cycles, an overcurrent is possible for a
certain time if afterwards an accordingly long recovery phase takes place. For both
utilisation cycles, a moving average is determined separately.
Monitoring of the device utilisation (I x t) activates the set error response (trip or warning
if one of the two utilisation values exceeds the limit of 100 %. The current device utilisation
(I x t) is displayed under parameter C00064/x:
C00064/1: Total value of the device utilisation
ƒ
C00064/2: Pulse utilisation in 15-s cycle
ƒ
C00064/3: Permanent utilisation in 180-s cycle
ƒ
Type of utilisation
Pulse utilisation
Permanent utilisation
EDS84ASC552 EN 10.0
Condition
Utilisation cycle
15 s
I
> 160 %
aNx
180 s
The monitoring function is
permanently active.
Technical data
Overcurrent operation
Monitoring function
Code
Display in C00064/2
Display of the maximum
value in C00064/1
Display in C00064/3
Display of the maximum
value in C00064/1