6
Electrical installation
HighLine C control terminals

Motor holding brake connection

6.8.4
Motor holding brake connection
Note!
If terminal X107 is used for connecting a motor holding brake, at least one
basic insulation to the motor or mains potential has to be provided, so that the
protective separation of the control terminals is not limited.
X107
Labelling
24B
GB
BD1
BD2
Terminal data
Flexible
With wire end ferrule
238
Description
Connection for external 24 V supply
voltage of the motor holding brake
Observe correct polarity!
GND connection for external supply
Pos. connection of the motor
holding brake (Lenze: WH)
Neg. connection of the motor
holding brake (Lenze: BN)
Conductor cross-section
2
[mm
]
0.2 ... 1.5
BD2
BD1
GB
X107
"
M
8400HLC037
DC 19.2 ... 28.8 V, IEC 61131-2
SELV/PELV
Example circuit  260
Tightening torque
[AWG]
[Nm]
24 ... 16
-
24B
DC 24 V
(+19.2...+28.8 V)
8400HLC045
[lb-in]
-
-
EDS84ASC552 EN 10.0