10
Safety engineering

Operating mode

10.5
Operating mode
With the integrated safety system, product key: ...B..., the following safety function can be
used:
Safe Torque Off (STO)
ƒ
If requested, the safe disconnection of the drive is achieved through:
Directly connected active sensors
ƒ
Passive sensors connected to a safety switching device
ƒ
The safety functions are suitable for applications according to IEC 61508 to SIL 3 and
achieve a performance level (PL) e and the control category 4 according to EN ISO 13849-1.
Danger!
If the request for the safety function is cancelled, the drive will restart
automatically.
You must provide external measures which ensure that the drive only restarts
after a confirmation (EN 60204).
The transmission of the pulse width modulation is safely switched (off) by the safety unit.
After this, the power drivers do not generate a rotating field. The motor is safely switched
to torqueless operation (STO).
μC
PWM
Fig. 10-1
278
X80
X80
SU
3x
C
P
3x
Operating principle of safety unit
SU
Safety unit
X80
Control terminals of safety unit (pluggable terminal strip)
C
Control section
C
Microcontroller
PWM
Pulse width modulation
P
Power section
M
Motor
M
EDS84ASC552 EN 10.0