Technical data
Standards and operating conditions
Electrical supply conditions
Motor connection
Requirements for the shielded motor cable
Capacitance per unit
length
Electric strength
Environmental conditions
Energy efficiency
High Efficiency
Climate
Storage
Transport
Operation
Site altitude
0 ... 1000 m ü. NN
1000 ... 4000 m ü. NN
Pollution
Vibration resistance
Transport
Operation
Electrical supply conditions
Power systems
TN
TT
48
< 150/300 pF/m
< 75/150 pF/m
Uo/U = 0.6/1.0 kV
UL
U ≥ 600 V
EN 50598-2
Class IE2
EN 60721-3-1
1K3 (-30 ... +60 °C)
EN 60721-3-2
2K3 (-30 ...+70 °C)
EN 60721-3-3
3K3 (-30 ... +55 °C)
EN 61800-5-1
Degree of pollution 2
UL 61800-5-1
EN 60721-3-2
2M2 (sine, shock)
Amplitude 0.075 mm
EN 61800-5-1
acceleration resistant up to 1
g
Amplitude 1 mm
German Lloyd
acceleration resistant up to
0.7 g
C core-core/C core-shield ≤ 4 mm² / AWG 12
C core-core/C core-shield ≤ 2.5 mm² / AWG 14
U = r.m.s. value from external conductor to external
conductor
Uo = r.m.s. value external conductor to PE
U = r.m.s. value from external conductor to external
conductor
Operation at a switching frequency of 2 or 4 kHz: Above
+45°C: reduce rated output current by 2.5 %/°C
Operation at a switching frequency of 8, 12 or 16 kHz:
Above +40°C: reduce rated output current by 2.5 %/°C
Reduce rated output current by 5 %/1000 m
in original packaging
10 ... 57 Hz
57 ... 150 Hz
5 ... 13.2 Hz
13.2 ... 100 Hz
Voltage to earth: max. 300 V