Safety Considerations
Power
DC Power Requirements
AC Power Cord Requirements by Country
64
Danger:
•
Only trained and qualified electrical service personnel should perform wiring and
cabling to the system.
•
All power to the equipment rack or cabinet should be disconnected before the
installation.
•
The power cables must be copper and meet your local electric code requirements.
•
The circuit breaker is not intended to be used as the chassis ON/OFF switch.
Disconnect the power from the power source to remove power.
•
The 7750 SR-a routers with DC PSU modules should be installed only in restricted
access areas (such as dedicated equipment rooms and electrical closets).
•
An external circuit breaker no greater than 60 A must be located within a readily
accessible distance of the equipment. This is intended as the disconnect device.
•
A disconnect device must be provided within 9.84 ft (3 m) of the 7750 SR-a chassis.
•
A #8 AWG (maximum) power conductor must be provided for each of the DC input
connections.
The following AC power cord requirements are applicable to all countries:
•
The length of the power cord must be at least 6 ft (1.8 m) and a maximum of
9.75 ft (3.0 m).
•
All power cords must be approved by an acceptable accredited agency responsible
for evaluation in the country where the power cord set is used.
•
The power cord must have a minimum current capacity of 10 A and a nominal
voltage rating of 220 or 240 VAC, as required by each country's power system. The
power cord must have a minimum current capacity of 12 A for 100V-120 VAC.
•
The appliance coupler must meet the mechanical configuration of an EN 60 320/IEC
320 Standard Sheet C13 connector for mating with appliance inlet on the unit.
•
The power cord set used with this 7750 SR-a must meet the local safety code and
requirements.
7750 SR-a4 and SR-a8 Installation Guide