Installing, Wiring, and Connecting a –48 VDC PSU
102
three lengths of #8 AWG wire, insulated and color-coded according to local safety
code, or #8 AWG jacketed three-conductor cord:
→ one ground wire, measured to extend from the PSU to the building ground point
or equipment bus ground point
→ one positive battery cable, measured to extend from the PSU to the positive
battery terminal
→ one negative battery cable, measured to extend from the PSU to the negative
battery terminal or disconnect device, if used
three single-hole terminal lugs for the three lengths of #8 AWG wire for connection
to the PSU
wire stripping tool
wire crimper
Phillips torque screwdriver
To prepare the PSU end of the ground cable:
Step 1. Using a wire-stripping tool, strip the wire insulation to the length according to the
recommendation of the terminal manufacturer or local safety code (Keys 1and 2 in
Figure
32).
Step 2. Attach the wire to the terminal ring and crimp the ring lug according to the
instructions of the terminal ring manufacturer (Key 3 in
Figure 32: Attaching the Ring Lug to a Ground Cable
3
Table 44: Ring Lug to Ground Cable Descriptions
Key
Description
1
#8 AWG copper wire (see Required tools and hardware)
2
Insulation stripped according to the recommendation of the manufacturer or local
safety code
3
Ring lug (see Required tools and hardware)
2
1
7750 SR-a4 and SR-a8 Installation Guide