Appendix E: Hazardous Area Installation; Instructions Specific To Hazardous Area Installations - Siemens Pointek CLS200 Digital Operating Instructions Manual

Capacitance switches
Hide thumbs Also See for Pointek CLS200 Digital:
Table of Contents

Advertisement

Appendix E: Hazardous Area Installation

WARNINGS:
• Turn off power before servicing any device.
• Please check the ambient and operating temperatures under
Environmental
configuration you are about to use or install.
• For intrinsically safe circuits, only certified current measuring devices
compatible with the transmitter may be used.
• In potentially explosive atmospheres:
- open the enclosure only when Pointek CLS200/300 is not
energized.
- if a transmitter is to be used as category 1/2 equipment, please
check the product nameplate, and see
Nameplates
• For intrinsically safe CLS200/300 models, power must be supplied from
an Intrinsically Safe power source, otherwise protection is no longer
guaranteed.
The transmitter is in operation when the power supply is switched on.
Note:
Instructions specific to hazardous area
installations
(Reference European ATEX Directive 94/9/EC, Annex II, 1/0/6)
The following instructions apply to equipment covered by certificate number KEMA
03ATEX1007X , KEMA 03ATEX1008X, KEMA 03ATEX1010X, KEMA 00ATEX2039X and KEMA
00ATEX2040X:
1.
For use and assembly, refer to the main instructions.
2.
The equipment is certified for use as Category 1G, 1/2G, 3G, 1/2D, 2D. Refer to appropriate
certificate.
3.
Refer to appropriate certificate for application in specific hazardous environment.
4.
Refer to appropriate certificate for ambient temperature range.
5.
The equipment has not been assessed as a safety related device (as referred to by
Directive 94/9/EC Annex II, clause 1.5).
6.
Installation and inspection of this equipment shall be carried out by suitably trained
personnel in accordance with the applicable code of practice (EN 60079-14 and EN 60079-
17 in Europe).
7.
Repair of this equipment shall be carried out by suitably trained personnel in accordance
with the applicable code of practice (e.g. EN 60079-19 within Europe).
7ML19985JJ03
on page 12, and
, page 89 onwards, to verify the protection type.
Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS
Process
on page 12 for the specific
Appendix D: Product
Page 91

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pointek cls300 digital

Table of Contents