Mode 24: Contact Type (Default: Close); Mode 25: Switch Point Off To On/Switch Point 1/Rising Edge (Default: 55%) - Siemens Pointek CLS200 Digital Operating Instructions Manual

Capacitance switches
Hide thumbs Also See for Pointek CLS200 Digital:
Table of Contents

Advertisement

Mode 24: Contact type (default: CLOSE)

The solid state switch alarm output can function in one of two ways:
Make contact (close)
Break contact (open)
To select the contact type.
Select Mode 24. The current contact type (OPEn or CLOSE) appears in the
primary reading field.
Press ⇑ or ⇓ to select the desired contact type.
Press M to save and exit.
WARNING: If you change this parameter, the position of the switch
changes immediately. Adapted applications or devices can react
unintentionally.
adjustment is independent of the Inversion Output parameter of the
Note: This
Discrete Input Function Block, which can only be set remotely.
Mode 25: Switch Point Off to On/Switch Point 1/Rising Edge
(default: 55%)
Initial setup can be carried out prior to mounting into the process, but it is
Note:
extremely important to calibrate the unit and adjust the sensitivity on the product itself.
Allows you to adjust the switch behavior by setting the percentage of the Application
Range (defined in Mode 19 and Mode 20) at which point the logical switch will change
from Off to On.
This symbol
Switch Point 1 must have a value greater than or equal to the value for Switch Point 2. If
you enter a lower value, Switch Point 2 will be adjusted to the same value.
The permitted range is limited by the distance of the Switch Point to the next Measuring
Limit.
To view the current setting for Switch Point 1:
Select Mode 25.
The current setting appears in the primary reading field as a percent of the
Application range (0 to 100%).
Press M to exit, or:
To adjust the setting:
Press ⇑ or ⇓.
The display switches to the current measured Sensor Value as a percent of the
Application Range (0 to 100%).
Press ⇑ or ⇓ to open Edit mode: the Sensor value is frozen.
Press ⇑ to edit the value of each digit, and press ⇓ to move the cursor to the
next digit.
Page 44
Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS
appears to the left of the numerical value to indicate a Rising Edge value.