Mode 4: Rise Time (default: 0.0 s)

Rise Time is a delay setting which adjusts the response time of the signal
becoming covered (Rising Edge). It affects the Primary Value of the Transducer Block.
Possible values range from 0.0 to 100.0 s, in 0.1 s intervals.
This symbol
to the left of the numerical value on the display indicates a Rise Time
setting.
To set Rise Time:
Select Mode 4.
Press ⇑ or ⇓ to open Edit Mode.
Press ⇑ to adjust the value digit by digit.
Press ⇓ to save the value.
Press M to exit.

Mode 5: Fall Time (default: 0.0 s)

Fall Time is a delay setting which adjusts the response time of the signal
becoming uncovered (Falling Edge). It affects the Primary Value of the Transducer Block.
Possible values range from 0.0 to 100.0 s, in 0.1 s intervals.
This symbol
to the left of the numerical value on the display indicates a Fall Time
setting.
To set Fall Time:
Select Mode 5.
Press ⇑ or ⇓ to open Edit Mode.
Press ⇑ to adjust the value digit by digit.
Press ⇓ to save the value.
Press M to exit.
1.
The bar graph, and numerical value in counts, continue to respond instantaneously to
changes in level.
7ML19985JJ03
Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS