Pointek CLS200 typical configuration with extensions:
For high or low level alarm:
•
designed for top mounting. The probe suspends vertically so that it reaches into
the process at the desired detection level (high or low detection alarm).
High level alarm
Mounting Restrictions
Note:
• Keep the sensor at least 50 mm (2") away from any nozzle or tank wall.
• If multiple units are used, allow at least 100 mm (4") between them, to prevent
interference.
In nozzle
Page 16
Pointek CLS200/300 Digital – OPERATING INSTRUCTIONS
normal process
level
Angle
50 mm (2")
minimum
> 100mm
Low level alarm
Close to tank walls
(4") Ø
50 mm (2") min
normal process
level
50 mm
(2")
min
7ML19985JJ03