SECTION 4

4.3.1.1 INPUT KEY

The INPUT Key is used to display the current status of all power source input
power parameters. It may be pressed any time while power is applied to the unit.
I1
displayed when the INPUT key is pressed.
NORMAL
ABNORMAL
FREQ
V
A
kW
kVA
I1: INPUT
(AB)NORMAL A
FREQ=XXX.X kVA

4.3.1.2 OUTPUT KEY

The OUTPUT Key is used to display the current status of all power source output
power parameters. It may be pressed any time power is applied to the unit. Any
one of several OUTPUT displays can be seen by pressing OUTPUT and one of
the function keys (f1-f4) as follows:
O1
displayed when the OUTPUT then f1 keys are pressed, showing basic
output parameters for that cabinet.
V
A
EFF
kW
FREQ
kVA
O1: CABINET V XXX/XXX XXX/XXX XXX/XXX
EFF=XX%
FREQ=XXX.X
Pacific Power Source ©2013
input power is acceptable.
input power is not acceptable.
input frequency.
input volts, phase to neutral / phase to phase.
input amps for each phase.
input kilowatts for each phase
input kilo-Volt-Amps for each phase.
V XXX/XXX XXX/XXX XXX/XXX
XXX
kW
XX.X
XX.X
output volts, phase to neutral / phase to phase
output amps for each phase.
single cabinet operating efficiency
single cabinet output kilowatts for each phase
output frequency
single cabinet output kilo-Volt-Amps for each phase.
OUTPUT A
XXX
kW
XX.X
kVA
4-6
XXX
XXX
XX.X
XX.X
XX.X
XX.X
XXX
XXX
XX.X
XX.X
XX.X XX.X XX.X
Document # 126050-10 Rev E
OPERATION