SECTION 3
3.7
CONNECTING THE OUTPUT SERVICE
When connecting the output service, certain requirements relating to safety are
stated in the following procedure and should be followed rigorously.
The standard output form of the MS-Series is 120/208Y, 50, 60, 400 Hz or
Variable frequency. Phase sequence of the output is ABC. Maximum output
current for each 3060-MS in a system is:
MODEL
NUMBER
3060-MS
The CE option incorporates output fuses F12-F14 in the mainframe cabinet. (No
output fuses are provided within the Cabinet in the standard configuration.)
Output connections in the standard MS-Series AC Power Source are made at the
output contactor terminals. Refer to figures 3.7, 3.7.1, 3.7.2 for location and
orientation of terminals.
The output terminals are compression type.
connections are clean and properly tightened.
screws to 150 in-lbs (17 N-m).
If the optional output circuit breaker is installed, connect the output wiring to the
output breaker.
Pacific Power Source ©2013
Output
Output RMS
(KVA)
(KW)
62.5
50
WARNING
ELECTROCUTION HAZARD
LETHAL VOLTAGES PRESENT AT OUTPUT OF MACHINE
REFER CONNECTION TO A QUALIFIED ELECTRICIAN.
3-15
INSTALLATION
Output
Output Short
(AMPS/Ø)
(AMPS/Ø)
175A
It is very important that the
Torque output connector set
Document # 126050-10 Rev E
Circuit
>350A