Inverter Module; Multi-Cabinet Paralleled System - Pacific Power Source MS SERIES Operation Manual

Table of Contents

Advertisement

SECTION 1

1.6.3 INVERTER MODULE

The inverter module is a solid-state device that converts power from the rectifier
circuit to provide the rated AC system output within specified limits.
The output frequency of the inverter is controlled by a digital oscillator.
The oscillator is adjustable over the range of 47 to 500Hz in the variable position.
In the fixed frequency positions, the oscillator is designed to control the inverter
output frequency within ±0.01%. Drift will not exceed ±0.01% during a 24-hour
period. Total frequency deviation, including short time fluctuations and drift, is
typically within ±0.01% from the specified frequency.
The inverter is capable of supporting transient overloads up to 150%, or any
continuous load within its rating, without reducing the output voltage. Loads
greater than 150% may cause a reduction of the output voltage.
The inverter will current limit at 150% of rated current. The inverter is capable of
supplying at least 200% of rated RMS current for short circuit conditions. If the
short circuit is sustained, the inverter will shut down and disconnect automatically
from the output.
Each inverter output phase voltage is independently regulated to ±0.5%, with
AGC enabled, such that unbalanced loading will not cause the output voltage to
exceed the specified voltage unbalance.
An output power filter is incorporated in the inverter unit. The filter reduces the
inverter output sine wave voltage harmonics to 1% RMS total and single
harmonics to 0.5% RMS maximum for linear loads at 50-60Hz.
Power semiconductors in the inverter unit are fused with fast acting fuses, so that
loss of any one power semiconductor will not cause cascading failures.

1.6.4 MULTI-CABINET PARALLELED SYSTEM

Up to twelve cabinets may be paralleled together for higher power systems.
Each 3060-MS is capable of operating as either a SLAVE or MASTER in multi-
cabinet parallel operation but only one Master may be active at a time.
Parallel system architecture is such that any failed slave unit automatically drops
off-line.
A failed MASTER turns the entire system off. In this event an operator can select
any other paralleled unit as the MASTER from a front panel control and restore
system operation.
Pacific Power Source ©2013
1-6
GENERAL
Document # 126050-10 Rev E

Advertisement

Table of Contents
loading

Table of Contents