Multiple Cabinet System - Pacific Power Source MS SERIES Operation Manual

Table of Contents

Advertisement

SECTION 3
3.8

MULTIPLE CABINET SYSTEM

When connecting the two or more cabinets in parallel to make a Multiple Cabinet
System, follow the procedure as described below.
Install each cabinet as a single cabinet power source with each cabinet next to
each other. No side clearance is necessary. Connect the input wiring to each
cabinet. See figure 3.8.1 for a Multiple Cabinet System Outline.
Connect a paralleling cable PN (126088) between each cabinet of the paralleled
system. Connect one cable from Cabinet #1-P2 to Cabinet #2-P1. Connect
another cable from Cabinet #2-P2 to Cabinet #3-P1, etc. Connect as many
paralleling cables (up to eleven for a twelve cabinet system) as needed. This
paralleling cable contains all of the control signals necessary to operate the
Multiple Cabinet System.
All five output wires (Chassis, Neutral, Phase A, Phase B and Phase C) from
each cabinet need to be paralleled.
Cabinet to the output load connection MUST BE THE SAME LENGTH AND
WIRE SIZE. Refer to figure 3.8.2 for Multiple Cabinet System Wiring.
WHEN THREE OR MORE CABINETS ARE CONNECTED IN PARALLEL, A
PARALLELING / OUTPUT LOAD CENTER WITH INDIVIDUAL CIRCUIT BREAKERS
FOR EACH CABINET MUST BE INSTALLED TO PROTECT OUTPUT WIRING AND
For three or more cabinets in parallel an Output Load Center is REQUIRED. The
Output Load Center must contain INDIVIDUAL CIRCUIT BREAKERS, one for
each 3060-MS unit. The circuit breaker must be sized for the individual cabinet's
output voltage and frequency. Pacific Power's Part Number 716048, a 175 Amp
Circuit Breaker may be used for standard 120/208 volt direct coupled output.
Refer to modification or option documentation for other output voltage forms and
frequencies.
Pacific Power Source ©2013
Each individual output wire from each
CAUTION
CABINETS.
3-18
INSTALLATION
Document # 126050-10 Rev E

Advertisement

Table of Contents
loading

Table of Contents