Specifications; Electrical Specifications; Input Power - Pacific Power Source MS SERIES Operation Manual

Table of Contents

Advertisement

SECTION 2
2.0

SPECIFICATIONS

Electrical and mechanical specifications of the MS Series AC Power Source are
listed in the following tables.
2.1

ELECTRICAL SPECIFICATIONS

2.1.1 INPUT POWER

MS-Series equipment is intended for use on a Category II supply.
Voltage:
Frequency:
Magnetizing Sub Cycle:
Power Factor:
Current Distortion:
Input Volts
480
416
400
380
240
208
Input Controls:
Protection:
Voltage Transients: Meets the Institute of Electrical and Electronics Engineers
Phase Rotation:
Isolation:
Balance:
Pacific Power Source ©2013
480, 416, 400, 380, 240 or 208 VAC
47-63 Hz (other frequencies optional)
100% of normal full load input, inrush current,
maximum.
Not less than 0.85 lagging at full load.
12% THD nominal
MODEL
INPUT
NUMBER
(KVA)
3060-MS
62
Recommended
Input Amps
Input Service
75
86
91
94
150
170
FIGURE 2.1.1
Contactors provide input ON-OFF control. An input circuit
breaker disconnects all input power from the cabinet.
Meets National Electrical Code Protection requirements for
single phase, and reversed-phase rotation protection.
587 requirements at 4000 V peak. Up to 150% line voltage
for ½-cycle.
Unit will operate properly with any input phase rotation.
There are no input phase rotation sensitive devices.
An input transformer with an electrostatic shield provides
isolation between the input and output of the system.
All three input phases are equally loaded regardless of
output phase load unbalance.
2-1
INPUT
(KW)
57
Taps Available
80 A
Nom, -7%, -10%
100 A
Nom, -9%, -4%, +3%, +8%
100 A
Nom, -9%, -5%, +4%, +8%
100 A
Nom, +5%, +10%, -4%, -8%,
-17%
175 A
Nom, -13%
175 A
Nom, +15%, -9%
INPUT RATINGS
Document # 126050-10 Rev E
SPECIFICATIONS
±15%.
L-L

Advertisement

Table of Contents
loading