APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 29 of 59)
ADDR
REGISTER NAME
7135
Ground Distance Zone 1 Delay
7136
Ground Distance Zone 1 Block
7138
Ground Distance Zone 1 Target
7139
Ground Distance Zone 1 Events
713A
Ground Distance Zone 1 Shape
713B
Ground Distance Zone 1 Z0 Z1 Magnitude
713C
Ground Distance Zone 1 Z0 Z1 Angle
713D
Ground Distance Zone 1 RCA
713E
Ground Distance Zone 1 DIR RCA
713F
Ground Distance Zone 1 DIR Comp Limit
7140
Ground Distance Zone 1 Quad Right Blinder
7141
Ground Distance Zone 1 Quad Right Blinder RCA
7142
Ground Distance Zone 1 Quad Left Blinder
7143
Ground Distance Zone 1 Quad Left Blinder RCA
7144
Ground Distance Zone 1 Z0M Z1 Magnitude
7145
Ground Distance Zone 1 Z0M Z1 Angle
7146
Ground Distance Zone 1 Voltage Level
7147
Ground Distance Zone 1 Non-Homogeneous Angle
7148
Ground Distance Zone 1 POL Current
7149
Ground Distance Zone 1 Reverse Reach
717A
Ground Distance Zone 1 Reverse Reach RCA
714B
Reserved (7 items)
7152
...Repeated for Ground Distance Zone 2
7174
...Repeated for Ground Distance Zone 3
Line Pickup (Read/Write Grouped Setting)
71E0
Line Pickup Function
71E1
Line Pickup Signal Source
71E2
Line Pickup Phase IOC Pickup
71E3
Line Pickup UV Pickup
71E4
Line End Open Pickup Delay
71E5
Line End Open Reset Delay
71E6
Line Pickup OV Pickup Delay
71E7
Autoreclose Coordination Pickup Delay
71E8
Autoreclose Coordination Reset Delay
71E9
Autoreclose Coordination Bypass
71EA
Line Pickup Block
71EC
Line Pickup Target
71ED
Line Pickup Events
71EE
Terminal Open
71F0
Autoreclose Accelerate
71F2
Line Pickup Distance Trip
Phase Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
7200
Phase Directional Overcurrent 1 Function
7201
Phase Directional Overcurrent 1 Source
7202
Phase Directional Overcurrent 1 Block
7204
Phase Directional Overcurrent 1 ECA
7205
Phase Directional Overcurrent 1 Pol V Threshold
7206
Phase Directional Overcurrent 1 Block Overcurrent
7207
Phase Directional Overcurrent 1 Target
7208
Phase Directional Overcurrent 1 Events
7209
Reserved (8 items)
7211
...Repeated for Phase Directional Overcurrent 2
GE Multilin
RANGE
0 to 65.535
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 10
-90 to 90
30 to 90
30 to 90
30 to 90
0.02 to 500
60 to 90
0.02 to 500
60 to 90
0 to 7
-90 to 90
0 to 5
-40 to 40
0 to 1
0.02 to 500
30 to 90
0 to 65535
0 to 1
0 to 5
0 to 30
0 to 3
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 1
0 to 4294967295
0 to 2
0 to 1
0 to 4294967295
0 to 4294967295
0 to 1
0 to 1
0 to 5
0 to 4294967295
0 to 359
0 to 3
0 to 1
0 to 2
0 to 1
0 to 1
L60 Line Phase Comparison System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F120
---
0.01
F001
degrees
1
F002
degrees
1
F001
degrees
1
F001
degrees
1
F001
ohms
0.01
F001
degrees
1
F001
ohms
0.01
F001
degrees
1
F001
---
0.01
F001
degrees
1
F002
pu
0.001
F001
degrees
0.1
F002
---
1
F521
ohms
0.01
F001
degrees
1
F001
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
pu
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
---
1
F102
---
1
F300
---
1
F109
---
1
F102
---
1
F300
---
1
F300
---
1
F102
---
1
F102
---
1
F167
---
1
F300
degrees
1
F001
pu
0.001
F001
---
1
F126
---
1
F109
---
1
F102
---
1
F001
DEFAULT
0
0
0 (Self-reset)
0 (Disabled)
0 (Mho)
B
270
0
85
85
90
1000
85
1000
85
0
0
0
0
0 (Zero-seq)
200
85
0
0 (Disabled)
0 (SRC 1)
1000
700
150
90
40
45
5
1 (Enabled)
0
0 (Self-reset)
0 (Disabled)
0
0
1 (Enabled)
0 (Disabled)
0 (SRC 1)
0
30
700
0 (No)
0 (Self-reset)
0 (Disabled)
0
B-37