B.4 MEMORY MAPPING
F001
UR_UINT16 UNSIGNED 16 BIT INTEGER
B
F002
UR_SINT16 SIGNED 16 BIT INTEGER
F003
UR_UINT32 UNSIGNED 32 BIT INTEGER (2 registers)
High order word is stored in the first register.
Low order word is stored in the second register.
F004
UR_SINT32 SIGNED 32 BIT INTEGER (2 registers)
High order word is stored in the first register.
Low order word is stored in the second register.
F011
UR_UINT16 FLEXCURVE DATA (120 points)
A FlexCurve is an array of 120 consecutive data points (x, y) which
are interpolated to generate a smooth curve. The y-axis is the
user-defined trip or operation time setting; the x-axis is the pickup
ratio and is pre-defined. See format F119 for a listing of the pickup
ratios; the enumeration value for the pickup ratio indicates the off-
set into the FlexCurve base address where the corresponding time
value is stored.
F013
POWER_FACTOR (SIGNED 16 BIT INTEGER)
Positive values indicate lagging power factor; negative values
indicate leading.
F050
UR_UINT32 TIME and DATE (UNSIGNED 32 BIT INTEGER)
Gives the current time in seconds elapsed since 00:00:00 January
1, 1970.
F051
UR_UINT32 DATE in SR format (alternate format for F050)
First 16 bits are Month/Day (MM/DD/xxxx).
Month: 1=January, 2=February,...,12=December.
Day: 1 to 31 in steps of 1.
Last 16 bits are Year (xx/xx/YYYY): 1970 to 2106 in steps of 1.
B-68
F052
UR_UINT32 TIME in SR format (alternate format for F050)
First 16 bits are Hours/Minutes (HH:MM:xx.xxx).
Hours: 0=12am, 1=1am,...,12=12pm,...23=11pm;
Minutes: 0 to 59 in steps of 1
Last
16
1=00.001,...,59999=59.999s)
F060
FLOATING_POINT IEEE FLOATING POINT (32 bits)
F072
HEX6 6 BYTES - 12 ASCII DIGITS
F073
HEX8 8 BYTES - 16 ASCII DIGITS
F074
HEX20 20 BYTES - 40 ASCII DIGITS
F081
ENUMERATION: AUTORECLOSE 1P/3P BKR FAIL OPTION
0 = Continue, 1 = Lockout
F082
ENUMERATION: AUTORECLOSE SINGLE-PHASE /
THREE-PHASE BREAKER SEQUENCE
0 = 1, 1 = 2, 2 = 1 & 2, 3 = 1 – 2, 4 = 2 – 1
F083
ENUMERATION: SELECTOR MODES
0 = Time-out, 1 = Acknowledge
F084
ENUMERATION: SELECTOR POWER UP
0 = Restore, 1 = Synchronize, 2 = Sync/Restore
F085
ENUMERATION: POWER SWING SHAPE
0 = Mho Shape, 1 = Quad Shape
F086
ENUMERATION: DIGITAL (CONTACT) INPUT DEFAULT STATE
0 = Off, 1 = On, 2= Latest/Off, 3 = Latest/On
L60 Line Phase Comparison System

B.4.2 DATA FORMATS

bits
are
Seconds
(xx:xx:.SS.SSS):
APPENDIX B
0=00.000s,