APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 33 of 59)
ADDR
REGISTER NAME
7FA7
Auxiliary Overvoltage 1 Target
7FA8
Auxiliary Overvoltage 1 Events
7FA9
Reserved (8 items)
7FB1
...Repeated for Auxiliary Overvoltage 2
7FC2
...Repeated for Auxiliary Overvoltage 3
Frequency (Read Only)
8000
Tracking Frequency
Temp Monitor Actual Values (Read Only Non-Volatile)
81C0
Reserved Register T1
81C1
Reserved Register T2
81C2
Reserved Register T3
81C4
Reserved Register T4
81C6
Reserved Register T5
81C8
Reserved Register T6
81CA
Reserved Register T7
81CC
Reserved Register T8
Breaker Failure (Read/Write Grouped Setting) (2 modules)
8600
Breaker Failure 1 Function
8601
Breaker Failure 1 Mode
8602
Breaker Failure 1 Source
8603
Breaker Failure 1 Amp Supervision
8604
Breaker Failure 1 Use Seal-In
8605
Breaker Failure 1 Three Pole Initiate
8607
Breaker Failure 1 Block
8609
Breaker Failure 1 Phase Amp Supv Pickup
860A
Breaker Failure 1 Neutral Amp Supv Pickup
860B
Breaker Failure 1 Use Timer 1
860C
Breaker Failure 1 Timer 1 Pickup
860D
Breaker Failure 1 Use Timer 2
860E
Breaker Failure 1 Timer 2 Pickup
860F
Breaker Failure 1 Use Timer 3
8610
Breaker Failure 1 Timer 3 Pickup
8611
Breaker Failure 1 Breaker Status 1 Phase A/3P
8613
Breaker Failure 1 Breaker Status 2 Phase A/3P
8615
Breaker Failure 1 Breaker Test On
8617
Breaker Failure 1 Phase Amp Hiset Pickup
8618
Breaker Failure 1 Neutral Amp Hiset Pickup
8619
Breaker Failure 1 Phase Amp Loset Pickup
861A
Breaker Failure 1 Neutral Amp Loset Pickup
861B
Breaker Failure 1 Loset Time
861C
Breaker Failure 1 Trip Dropout Delay
861D
Breaker Failure 1 Target
861E
Breaker Failure 1 Events
861F
Breaker Failure 1 Phase A Initiate
8621
Breaker Failure 1 Phase B Initiate
8623
Breaker Failure 1 Phase C Initiate
8625
Breaker Failure 1 Breaker Status 1 Phase B
8627
Breaker Failure 1 Breaker Status 1 Phase C
8629
Breaker Failure 1 Breaker Status 2 Phase B
862B
Breaker Failure 1 Breaker Status 2 Phase C
862D
...Repeated for Breaker Failure 2
FlexState Settings (Read/Write Setting)
8800
FlexState Parameters (256 items)
GE Multilin
RANGE
0 to 2
0 to 1
0 to 65535
2 to 90
-55 to 125
-55 to 125
-2147483647 to
2147483647
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
0 to 1
0 to 5
0 to 1
0 to 1
0 to 4294967295
0 to 4294967295
0.001 to 30
0.001 to 30
0 to 1
0 to 65.535
0 to 1
0 to 65.535
0 to 1
0 to 65.535
0 to 4294967295
0 to 4294967295
0 to 4294967295
0.001 to 30
0.001 to 30
0.001 to 30
0.001 to 30
0 to 65.535
0 to 65.535
0 to 2
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
L60 Line Phase Comparison System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F109
---
1
F102
---
1
F001
Hz
0.01
F001
C
1
F002
C
1
F002
---
1
F004
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F102
---
1
F157
---
1
F167
---
1
F126
---
1
F126
---
1
F300
---
1
F300
pu
0.001
F001
pu
0.001
F001
---
1
F126
s
0.001
F001
---
1
F126
s
0.001
F001
---
1
F126
s
0.001
F001
---
1
F300
---
1
F300
---
1
F300
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
s
0.001
F001
s
0.001
F001
---
1
F109
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
DEFAULT
0 (Self-reset)
0 (Disabled)
0
B
0
-55
125
0
0
0
0
0
0
0 (Disabled)
0 (3-Pole)
0 (SRC 1)
1 (Yes)
1 (Yes)
0
0
1050
1050
1 (Yes)
0
1 (Yes)
0
1 (Yes)
0
0
0
0
1050
1050
1050
1050
0
0
0 (Self-reset)
0 (Disabled)
0
0
0
0
0
0
0
0
B-41