5.5 GROUPED ELEMENTS
POS SEQ di/dt FDL PICKUP: This setting controls pickup of the low set stage of the element used to control the key
operation. Nominal current of the phase CT bank of the relay is 1 pu.
POS SEQ di/dt FDL SEAL-IN: This setting defines seal-in time of the FDL function. To equalize the response between
all terminals of the line, the timer is started at the rising edge of the raw di / dt condition.
POS SEQ di/dt FDH PICKUP: This setting controls pickup of the high set stage of the element used to control the trip
operation. Nominal current of the phase CT bank of the relay is 1pu.
POS SEQ di/dt FDH SEAL-IN: This setting defines seal-in time of the function. To equalize the response between all
terminals of the line, the timer is started at the rising edge of the raw di / dt condition. In this way, the fault detectors
reset approximately at the same time at all line terminals, regardless of responses of individual raw conditions poten-
tially different at different line terminals.
POS SEQ FDH SUPV: This setting provides seal-in control of the FDH function for the symmetrical external three-
phase faults starting as non-symmetrical defined by the
tance function should typically be assigned with this setting.
POS SEQ di/dt BLK: Note that the fault detector is hard-wired to the 87PC scheme. It can be disabled permanently
using the function setting, or blocked temporarily using this block setting. Select a FlexLogic operand that, if asserted,
should block this fault detector.
POS SEQ di/dt FD TARGET: This setting controls targets of the function. These targets operate independently from
the 87PC targets.
POS SEQ di/dt FD EVENTS: This setting controls event recording of the function. These events are logged indepen-
dently from the 87PC events.
SETTINGS
5
POS SEQ di/dt
FD FUNCTION:
Enabled = 1
POS SEQ di/dt
BLK:
Off = 0
FAST MEASUREMENTS
F1 PHASE CT BANK:
Pos-seq current, I_1
L1 PHASE CT BANK:
Pos-seq current, I_1
SETTINGS
POS SEQ FDH
SUPV:
Off = 0
Figure 5–52: POSITIVE-SEQUENCE CURRENT RATE OF CHANGE FAULT DETECTOR LOGIC
5-138
POS SEQ DI/DT FDH SEAL-IN
SETTINGS
POS SEQ di/dt
FDL PICKUP:
POS SEQ di/dt
FDH PICKUP:
RUN
| I_1 - I_1* |
> FDL PICKUP
Σ
(summed
> FDH PICKUP
current)
(*) value delayed
by 0.5 cycle
L60 Line Phase Comparison System
setting time. The overreaching dis-
Hardwired to the
TIMERS
87PC function
POS SEQ di/dt
FLEXLOGIC
FDL SEAL-IN:
OPERANDS
0
87PC dI1/dt FDL OP
t
DPO
87PC dI1/dt FDH OP
POS SEQ di/dt
FDH SEAL-IN:
0
t
DPO
831801A2.CDR
5 SETTINGS