GE L60 Instruction Manual page 588

Line phase comparison system ur series
Hide thumbs Also See for L60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 22 of 59)
ADDR
REGISTER NAME
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (4 modules)
5DA0
Ground Instantaneous Overcurrent 1 Function
5DA1
Ground Instantaneous Overcurrent 1 Signal Source
5DA2
Ground Instantaneous Overcurrent 1 Pickup
5DA3
Ground Instantaneous Overcurrent 1 Delay
B
5DA4
Ground Instantaneous Overcurrent 1 Reset Delay
5DA5
Ground Instantaneous Overcurrent 1 Block
5DA7
Ground Instantaneous Overcurrent 1 Target
5DA8
Ground Instantaneous Overcurrent 1 Events
5DA9
Reserved (8 items)
5DB1
...Repeated for Ground Instantaneous Overcurrent 2
5DC2
...Repeated for Ground Instantaneous Overcurrent 3
5DD3
...Repeated for Ground Instantaneous Overcurrent 4
CT Fail (Read/Write Setting) (6 modules)
5E6C
CT Fail 1 Function
5E6D
CT Fail 1 Block
5E6F
CT Fail 1 Current Source 1
5E70
CT Fail 1 Current Pickup 1
5E71
CT Fail 1 Current Source 2
5E72
CT Fail 1 Current Pickup 2
5E73
CT Fail 1 Voltage Source
5E74
CT Fail 1 Voltage Pickup
5E75
CT Fail 1 Pickup Delay
5E76
CT Fail 1 Target
5E77
CT Fail 1 Events
5E78
...Repeated for CT Fail 2
5E84
...Repeated for CT Fail 3
5E90
...Repeated for CT Fail 4
5E9C
...Repeated for CT Fail 5
5EA8
...Repeated for CT Fail 6
Setting Groups (Read/Write Setting)
5F70
Setting Group for Modbus Comms (0 means group 1)
5F71
Setting Groups Block
5F73
FlexLogic Operands to Activate Groups 2 through 6 (5
items)
5F7D
Setting Group Function
5F7E
Setting Group Events
Setting Groups (Read Only)
5F7F
Current Setting Group
Setting Group Names (Read/Write Setting)
5F8C
Setting Group 1 Name
5F94
Setting Group 2 Name
5F9C
Setting Group 3 Name
5FA4
Setting Group 4 Name
5FAC
Setting Group 5 Name
5FB4
Setting Group 6 Name
Phase Comparison Negative Sequence Voltage (Read/Write Grouped Setting)
6070
Negative Sequence Voltage FD Function
6071
Negative Sequence Voltage FD Impedance
6072
Negative Sequence Voltage FDL Pickup
6073
Negative Sequence Voltage FDH Pickup
6074
Negative Sequence Voltage FD Block
6076
Negative Sequence Voltage FD Target
6077
Negative Sequence Voltage FD Events
B-30
RANGE
0 to 1
0 to 5
0 to 30
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 1
0 to 4294967295
0 to 5
0 to 2
0 to 5
0 to 2
0 to 5
0 to 2
0 to 65.535
0 to 2
0 to 1
0 to 5
0 to 4294967295
0 to 4294967295
0 to 1
0 to 1
0 to 5
---
---
---
---
---
---
0 to 1
0 to 100
0.005 to 3
0.005 to 3
0 to 4294967295
0 to 2
0 to 1
L60 Line Phase Comparison System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F300
---
1
F167
pu
0.1
F001
---
1
F167
pu
0.1
F001
---
1
F167
pu
0.01
F001
s
0.001
F001
---
1
F109
---
1
F102
---
1
F001
---
1
F300
---
1
F300
---
1
F102
---
1
F102
---
1
F001
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
1
F102
%
0.1
F001
pu
0.001
F001
pu
0.001
F001
---
1
F300
---
1
F109
---
1
F102
DEFAULT
0 (Disabled)
0 (SRC 1)
1000
0
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0
0 (SRC 1)
2
1 (SRC 2)
2
0 (SRC 1)
20
1000
0 (Self-reset)
0 (Disabled)
0
0
0
0 (Disabled)
0 (Disabled)
0
(none)
(none)
(none)
(none)
(none)
(none)
0 (Disabled)
100
10
50
0
0 (Self-reset)
0 (Disabled)
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents